F-Gas English Low GWP

All questions
HFC | Flammable | CO₂ | NH₃
Easy questions | Medium questions | Difficult questions

1

Difficult

What is the main difference between a dry-expansion and a flooded evaporator?


In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)
A dry-expansion evaporator always has a lower pressure than a flooded one
A dry-expansion evaporator needs no expansion valve, a flooded one does
A dry-expansion evaporator is filled with liquid, a flooded one with vapour

2

Difficult

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Atmospheric pressure, approx. 1 bar abs
Positive pressure of 10–20 bar
Positive pressure of 5–10 bar
Below atmospheric (approx. 0.7 bar abs at −40 °C)

3

Difficult

How is oil managed in R717 systems?


Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer
Oil requires no monitoring
Oil has no effect on system operation
Oil can be mixed with any refrigerant

4

Difficult

What should be done with contaminated R717?


Purify it or send it for disposal in accordance with regulations
Release it into the atmosphere
Dilute it with water and reuse it
Continue to use it without restriction

5

Difficult

What should be done if an NH₃ leak is detected?


Carry on working with the room door open
Increase the pressure in the system
Carry on working wearing a dust mask
Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)

6

Difficult

What role do scrubbers play in NH₃ systems?


Neutralise ammonia through absorption in a liquid (e.g. water)
They are used to measure temperature
They store the refrigerant
They increase the pressure in the system

7

Difficult

How should the system be prepared before filling with R717?


The pressure must be increased above the standard level
Simply start it up
There is no need to check it
Check for leaks, remove air and moisture, and create a vacuum

8

Difficult

What are the transport requirements for R717?


It can be carried in open containers
Transport is not regulated
It can be carried without labelling
It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)

9

Difficult

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 mixes very well with the oil, which easily returns to the compressor
R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)
R717 does not mix with the oil; the oil collects on the high-pressure side above the R717
An oil return line cannot be used in R717 systems because the oil is too hot

10

Difficult

Which refrigerant can be detected with phenolphthalein paper?


R1234ze(E)
R717
R744
R1270

11

Difficult

Which system may require manual oil recovery?


An R717 system
R744 cascade system
Supercritical ‘booster’ system using R744
Secondary system using R744

12

Difficult

Which refrigerant is lighter than air?


R744
R1234ze(E)
R1270
R717

13

Difficult

R717 is highly corrosive to:


copper (and its alloys)
aluminium
titanium
stainless steel

14

Difficult

What is the recommended pre-alarm level for fixed leak detection systems for R717?


50,000 ppm
500 ppm
5,000 ppm
500,000 ppm

15

Difficult

Why are compressors with a separate motor (open type) mostly used in R717 systems?


To lower the condensing pressure
Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used
Because they are cheaper
To increase the refrigerant charge

16

Difficult

Which type of compressor is most commonly used in large ammonia systems?


A reciprocating or screw compressor
Diaphragm compressor
Hermetic scroll
Rotary vane compressor

17

Difficult

How is the capacity of a piston compressor regulated in NH₃ systems?


Solely by adjusting the oil volume
By unloading the cylinders or changing the rotational speed
By increasing the condensing pressure
By reducing the refrigerant charge

18

Difficult

How is the capacity of a screw compressor most commonly controlled?


By using a slide valve
By closing the suction valve
By adjusting the oil level
By changing the type of oil

19

Difficult

When is two-stage compression used in NH₃ systems?


Only with water-cooled condensers
At small temperature differences
Only in small systems
At low evaporating temperatures (pressures) and high pressure ratios

20

Difficult

What is the advantage of two-stage compression over single-stage compression?


No need for a separator
Higher efficiency and lower discharge temperature
Higher energy consumption
Lower efficiency

21

Difficult

How does an evaporative condenser used in NH₃ systems work?


It utilises the evaporation of water to increase cooling efficiency
Operates without a fan
It does not require a water supply
It transfers heat only to the air

22

Difficult

What is the function of the liquid separator in an NH₃ system?


Regulates the condensing pressure
It separates oil from the refrigerant
It prevents liquid from entering the compressor
Increases the discharge temperature

23

Difficult

What is the purpose of monitoring the liquid level in the separator?


To reduce the condensing temperature
To increase the oil volume
To control the condenser fan
To maintain the correct refrigerant level and prevent the compressor from flooding

24

Difficult

What is the role of the float switch in NH₃ systems?


It monitors the liquid level in the tank or separator
It controls the fan’s operation
It regulates the condensation temperature
It is used to detect leaks

25

Difficult

What is a thermosyphon in NH₃ systems?


An oil circulation pump
A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling
A type of safety valve
A defrosting device

26

Difficult

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


Because NH₃ does not mix with most compressor oils
Because the oil mixes only with water
To increase the amount of refrigerant
To reduce the pressure

27

Difficult

What is the main function of an oil separator in NH₃ systems?


Removing moisture from the system
To lower the condensation temperature
To separate the oil from the refrigerant and return the oil to the compressor
To increase fan efficiency

28

Difficult

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


A glycol system
A pumped liquid-recirculation system
An indirect system
A direct-expansion (DX) system

29

Difficult

What is the characteristic feature of a flooded evaporator system?


The evaporator contains a large amount of liquid, which improves heat transfer
The evaporator is filled exclusively with vapour
No separator is used
No level control is required

30

Difficult

What is the main difference between a direct and an indirect system?


In an indirect system, no compressor is used
In a direct system, there is no evaporator
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In an indirect system, NH₃ flows directly into the space being cooled