What is the main difference between a dry-expansion and a flooded evaporator?


A dry-expansion evaporator is filled with liquid, a flooded one with vapour
A dry-expansion evaporator always has a lower pressure than a flooded one
In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)
A dry-expansion evaporator needs no expansion valve, a flooded one does

2

Ťažká

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Below atmospheric (approx. 0.7 bar abs at −40 °C)
Positive pressure of 5–10 bar
Atmospheric pressure, approx. 1 bar abs
Positive pressure of 10–20 bar

3

Ťažká

How is oil managed in R717 systems?


Oil can be mixed with any refrigerant
Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer
Oil requires no monitoring
Oil has no effect on system operation

4

Ťažká

What should be done with contaminated R717?


Dilute it with water and reuse it
Continue to use it without restriction
Release it into the atmosphere
Purify it or send it for disposal in accordance with regulations

5

Ťažká

What should be done if an NH₃ leak is detected?


Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)
Carry on working wearing a dust mask
Increase the pressure in the system
Carry on working with the room door open

6

Ťažká

What role do scrubbers play in NH₃ systems?


They store the refrigerant
They are used to measure temperature
Neutralise ammonia through absorption in a liquid (e.g. water)
They increase the pressure in the system

7

Ťažká

How should the system be prepared before filling with R717?


The pressure must be increased above the standard level
There is no need to check it
Check for leaks, remove air and moisture, and create a vacuum
Simply start it up

8

Ťažká

What are the transport requirements for R717?


It can be carried in open containers
It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)
It can be carried without labelling
Transport is not regulated

9

Ťažká

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 does not mix with the oil; the oil collects on the high-pressure side above the R717
R717 mixes very well with the oil, which easily returns to the compressor
R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)
An oil return line cannot be used in R717 systems because the oil is too hot

10

Ťažká

Which refrigerant can be detected with phenolphthalein paper?


R744
R1270
R1234ze(E)
R717

11

Ťažká

Which system may require manual oil recovery?


An R717 system
Supercritical ‘booster’ system using R744
R744 cascade system
Secondary system using R744

12

Ťažká

Which refrigerant is lighter than air?


R744
R1270
R717
R1234ze(E)

13

Ťažká

R717 is highly corrosive to:


titanium
stainless steel
copper (and its alloys)
aluminium

14

Ťažká

What is the recommended pre-alarm level for fixed leak detection systems for R717?


500,000 ppm
500 ppm
5,000 ppm
50,000 ppm

15

Ťažká

Why are compressors with a separate motor (open type) mostly used in R717 systems?


Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used
To increase the refrigerant charge
Because they are cheaper
To lower the condensing pressure

16

Ťažká

Which type of compressor is most commonly used in large ammonia systems?


A reciprocating or screw compressor
Hermetic scroll
Diaphragm compressor
Rotary vane compressor

17

Ťažká

How is the capacity of a piston compressor regulated in NH₃ systems?


By increasing the condensing pressure
Solely by adjusting the oil volume
By unloading the cylinders or changing the rotational speed
By reducing the refrigerant charge

18

Ťažká

How is the capacity of a screw compressor most commonly controlled?


By changing the type of oil
By adjusting the oil level
By closing the suction valve
By using a slide valve

19

Ťažká

When is two-stage compression used in NH₃ systems?


At low evaporating temperatures (pressures) and high pressure ratios
Only in small systems
At small temperature differences
Only with water-cooled condensers

20

Ťažká

What is the advantage of two-stage compression over single-stage compression?


No need for a separator
Lower efficiency
Higher efficiency and lower discharge temperature
Higher energy consumption

21

Ťažká

How does an evaporative condenser used in NH₃ systems work?


It does not require a water supply
Operates without a fan
It utilises the evaporation of water to increase cooling efficiency
It transfers heat only to the air

22

Ťažká

What is the function of the liquid separator in an NH₃ system?


Increases the discharge temperature
Regulates the condensing pressure
It separates oil from the refrigerant
It prevents liquid from entering the compressor

23

Ťažká

What is the purpose of monitoring the liquid level in the separator?


To control the condenser fan
To increase the oil volume
To maintain the correct refrigerant level and prevent the compressor from flooding
To reduce the condensing temperature

24

Ťažká

What is the role of the float switch in NH₃ systems?


It controls the fan’s operation
It is used to detect leaks
It regulates the condensation temperature
It monitors the liquid level in the tank or separator

25

Ťažká

What is a thermosyphon in NH₃ systems?


A type of safety valve
An oil circulation pump
A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling
A defrosting device

26

Ťažká

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To increase the amount of refrigerant
Because the oil mixes only with water
To reduce the pressure
Because NH₃ does not mix with most compressor oils

27

Ťažká

What is the main function of an oil separator in NH₃ systems?


To lower the condensation temperature
To increase fan efficiency
Removing moisture from the system
To separate the oil from the refrigerant and return the oil to the compressor

28

Ťažká

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


A direct-expansion (DX) system
A pumped liquid-recirculation system
A glycol system
An indirect system

29

Ťažká

What is the characteristic feature of a flooded evaporator system?


No level control is required
The evaporator is filled exclusively with vapour
The evaporator contains a large amount of liquid, which improves heat transfer
No separator is used

30

Ťažká

What is the main difference between a direct and an indirect system?


In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In an indirect system, no compressor is used
In an indirect system, NH₃ flows directly into the space being cooled
In a direct system, there is no evaporator