F-Gas English Low GWP

All questions
HFC | Flammable | CO₂ | NH₃
Easy questions | Medium questions | Difficult questions

1

Easy


2

Easy

What is the base unit of mass in the International System of Units (SI)?


t
lb (pound)
N
kg

3

Medium

What process takes place in the condenser of a refrigeration system?


Hot vapour discharged by the compressor is desuperheated, condensed, and the resulting liquid is slightly subcooled
The refrigerant absorbs heat from the surroundings and evaporates
The secondary fluid (glycol, water) condenses while the refrigerant evaporates
The refrigerant rejects only the heat generated in the compressor

4

Medium

What mainly determines the condensing temperature of an air-cooled condenser?


The compressor discharge temperature
The evaporating temperature
The superheat
The ambient (inlet) air temperature

5

Medium

Why does heat flow from the condenser to the surroundings?


Because the compressor pushes heat directly into the surroundings
Because the pressure in the condenser is lower than ambient
Because the condensing temperature is higher than the ambient temperature, and heat flows spontaneously from a warmer to a colder body (second law of thermodynamics)
Because HFC refrigerants attract heat from the surroundings

6

Medium

What should you mainly pay attention to when operating a condenser?


Its general condition and the cleanliness of the heat-exchange surfaces
The colour of the condenser casing
That the inlet air temperature is lower than the outlet air temperature
That the outlet air temperature is higher than the condensing temperature

7

Medium

What criteria should be considered when selecting a suitable condenser?


Only the size and number of fans
Only own experience and the dimensions
Fan noise, connection diameters and colour
The required capacity of the condenser and the technical specifications declared by the manufacturer

8

Medium

How do contaminants (dust, particulates, deposits) affect the performance and efficiency of heat exchange surfaces in condensers?


Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause an increase in condensing temperature and pressure, which in turn leads to a reduction in the condenser’s efficiency.
Contaminants increase the heat transfer area and reduce the condensing pressure.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause a reduction in condensing pressure.
Contaminants do not significantly affect the efficiency and effectiveness of the heat exchange surfaces in condensers.

9

Medium

How does the capacity of an air-cooled condenser change when it becomes dirty?


It increases
It decreases
It increases because the fan speed rises
It remains unchanged

10

Medium

What is the main consequence of heavy frost on an air-cooling evaporator?


A rise in the cooled-air temperature with no effect on capacity
A rise in evaporating pressure
An increase in condenser subcooling
Reduced heat transfer and airflow, resulting in a drop in cooling capacity and evaporating temperature

11

Medium

What happens when the evaporation temperature drops?


The discharge temperature decreases.
The condenser fan speed increases.
The compressor’s cooling capacity increases.
The compressor’s cooling capacity decreases.

12

Medium

When is natural (off-cycle, air) defrosting possible?


Only in freezer rooms below −18 °C
When the air passing through the cooler is above 0 °C
Only in coolers fitted with speed-controlled fans
Never – electric heaters must be used in every air cooler

13

Medium

When does frost form on the surface of an air-cooling evaporator?


Only when the room air temperature falls below 0 °C
Only when the system runs continuously
When the evaporator surface temperature is below 0 °C and below the dew point of the air
Always, in every air cooler

14

Medium

In extensive pipework systems, flash gas (secondary evaporation) in the liquid line can be prevented by…


…using smaller-diameter pipes
…insulating the discharge line between the compressor and the condenser
…additional subcooling of the liquid
…increasing the length of the liquid line

15

Medium

How does hot gas defrosting of the evaporator work?


We switch on the gas heater directed at the evaporator.
Heated vapour (hot gas) from the compressor is directed into the evaporator piping.
This involves reversing the direction of rotation of the compressor.
We swap the outlet and inlet sides of the evaporator.

16

Medium

What is the function of the evaporator in a refrigeration system?


It evaporates the water flowing through the evaporator.
It ensures that the refrigerant is superheated over the largest possible heat exchange surface area.
It cools the refrigerant.
It transfers heat from the medium being cooled to the boiling refrigerant.

17

Medium

What condition must electric heaters for evaporator defrosting meet?


They must be located beneath the evaporator
They must have good thermal contact with the heat-exchange surface (e.g. inserted in the fin block)
Heat from the heaters must be carried by the running fans
They must be in direct contact with the refrigerant

18

Medium

Refrigerant distributor:


ensures even distribution of the refrigerant to the individual sections of the condenser.
acts as a buffer for the refrigerant in the event that the pressure upstream of the expansion valve is exceeded.
ensures the even distribution of the refrigerant discharged by compressors connected in parallel.
ensures an even distribution of the refrigerant to the individual sections of the evaporator.

19

Medium

What defrosting methods are used for air coolers?


Electric only – other methods are not permitted in refrigeration
Natural only – other methods are ineffective and uneconomic
Only by switching off the fans with the compressor running
Electric, hot gas, water spray and natural (at positive temperatures)

20

Medium

The boiling point of a liquid rises when the pressure above the liquid…


…remains constant
…rises
…falls
…varies depending on the ambient temperature

21

Medium

MOP in thermostatic expansion valves stands for:


minimum flow opening.
self-cleaning of the valve in the event of moisture in the refrigerant freezing.
maximum pressure switch protection.
maximum operating pressure.

22

Medium

The function of a thermostatic expansion valve (TEV) is:


to maintain a constant condensing pressure
to meter refrigerant into the evaporator according to the superheat of the vapour leaving the evaporator
to maintain a constant compressor suction pressure
to adjust the evaporating pressure in the condenser

23

Medium

What type of compressor motor can be used with a capillary tube?


An electronically commutated motor
A low-speed motor
A low-starting-torque motor (pressures equalise during standstill)
A high-starting-torque motor must be used

24

Medium

What does a thermostatic expansion valve control?


The mass flow of refrigerant fed into the evaporator
The condensing pressure
The temperature in the cold room
The discharge temperature

25

Easy

The refrigerant absorbs heat when…


…it condenses
…it evaporates
…it freezes
…it is subcooled

26

Medium

What does the manufacturer state as the factory setting of a thermostatic expansion valve?


the static superheat of the valve.
the superheat value during valve operation.
the degree of refrigerant expansion.
the degree to which the valve is filled with refrigerant liquid.

27

Medium

Where is a new or repaired system with an expansion valve and liquid receiver charged?


Through the capillary tube outlet during normal system operation
Anywhere – the charging point does not matter
In the liquid phase on the high-pressure side, with the compressor stopped
In the liquid phase into the compressor suction, with the compressor running

28

Medium

What does a thermostatic or electronic expansion valve control?


The compressor speed
Subcooling, by adjusting condensing pressure
The evaporating pressure – closing below the set point
The amount of refrigerant fed to the evaporator according to superheat

29

Medium

What does the MOP function of thermostatic expansion valves mean?


The valve limits the maximum evaporating (suction) pressure, protecting the compressor motor from overload, e.g. after defrost
The valve limits subcooling
The valve maintains a constant condensing pressure
The valve prevents motor overheating by injecting liquid into the compressor

30

Medium

The lower the liquid temperature upstream of the expansion valve, (at the same mass flow)…


…the higher the specific refrigerating effect qo [kJ/kg] and the higher the cooling capacity Qo
…the lower qo, with Qo unchanged
…the lower qo and the lower Qo
…the lower qo and the lower energy efficiency

31

Medium

How should the MOP point of an expansion valve be selected relative to the highest normal evaporating temperature?


Freely – the MOP value is irrelevant
Higher by approx. 20 K
A few kelvin higher (approximately 7 K)
About 7 K lower than that temperature

32

Medium

What is the function of the suction pressure regulator?


It limits the suction pressure and protects the compressor from excessively high suction pressure.
It prevents a drop in suction pressure and, if necessary, shuts down the refrigeration system.
To maintain the suction pressure at the highest possible level.
It maintains the evaporation pressure at a constant level.

33

Medium

What is the function of the valve regulating water flow through the condenser?


To maintain the condensing pressure at the highest possible level.
To maintain the condensing pressure at a constant level.
To maintain the water temperature at the highest level.
To maintain the condensing pressure at the lowest possible level.

34

Medium

The use of a refrigerant distributor requires a thermostatic expansion valve ...


... with internal pressure equalisation.
... with a MOP function.
... with an adsorption-type sensor filling.
... with external pressure equalisation.

35

Medium

What properties should good insulation materials have?


The ability to absorb large amounts of moisture
An antistatic coating
High thermal conductivity
Low thermal conductivity (and low water absorption, vapour tightness)

36

Medium

When is refrigerant vapour superheated?


When the pressure on the discharge side is higher than on the suction side
When the compressor motor temperature rises excessively
When its temperature is higher than the saturation temperature corresponding to its pressure
When the evaporating temperature is lower than the ambient temperature

37

Medium

How can you check whether the liquid refrigerant is reaching the expansion valve without vapour bubbles?


We check using a pressure gauge fitted on the discharge side of the compressor.
We check this using a sight glass.
We check using a liquid pressure gauge.
We are unable to check this.

38

Medium

Where does the liquid line run?


From the condenser (liquid receiver) to the expansion valve
Between the evaporator and the suction-line heat exchanger
Between the evaporator and the compressor
Between the compressor and the condenser

39

Medium

What is the function of the liquid receiver in a refrigeration system?


To act as a reserve when the required charge is unknown
To further subcool the condensed refrigerant
To collect liquid refrigerant and excess oil
To store refrigerant and compensate for changes in the circulating charge as the heat load varies

40

Medium

What is the purpose of the liquid receiver during service work?


It further subcools the refrigerant before the expansion valve
It allows pump-down and temporary storage of the refrigerant
It collects excess oil circulating in the system
It is a reserve when the installer does not know the required charge

41

Medium

Where should the liquid receiver be installed?


It should be fitted after the evaporator.
It should be fitted just before the compressor.
It should be fitted between the compressor and the condenser.
It should be installed downstream of the condenser, upstream of the expansion valve.

42

Medium

What is the function of the suction pressure regulator fitted to the suction pipe when the compressor starts up?


It regulates the evaporation pressure.
It closes when the suction pressure upstream of the compressor drops.
It regulates the condensing pressure.
It opens when the suction pressure upstream of the compressor drops.

43

Medium

The use of microchannel heat exchangers, compared with conventional heat exchangers made of copper tubes and fins, results in:


An increase in the amount of refrigerant in the system and an increase in condensing pressure.
There is no effect whatsoever on either the amount of refrigerant or energy efficiency.
A reduction in the system’s energy efficiency.
A reduction in refrigerant charge and, typically, higher energy efficiency.

44

Medium

Which refrigerants belong to the HFC group?


R11, R12, R502.
R134a, R404A, R507A, R410A.
R134a, R32, R22, R507A, R290.
R22, R401A.

45

Medium

Which refrigerants belong to the HFO group?


R134a, R404A.
R134a, R290.
R22, R12.
R1234yf, R1234ze(E).

46

Medium

What are the characteristics of R410A refrigerant compared to R407C refrigerant?


The saturation pressure of R407C refrigerant is much higher than that of R410A.
The saturation pressure of both refrigerants is roughly the same.
The saturation pressure of R410A refrigerant is higher than that of R407C.
The saturation pressure of R407C is 150% higher than that of R410A.

47

Medium

What does the TEWI indicator define?


Total Equivalent Warming Impact: the sum of direct emissions (leakage and refrigerant losses at disposal) and indirect emissions (CO₂ from generating the energy consumed by the equipment) over its lifetime
The ability of the ozone layer to recover
The global warming potential of a gas relative to CO₂ over a 100-year horizon
The impact of a refrigerant on the ozone layer

48

Medium

What are the characteristics of R452A compared with R404A?


The temperature glide of R452A is half that of R404A
It is a flammable and toxic single-component HFC
Both are azeotropic and have no temperature glide
It is a non-flammable (A1) HFC/HFO blend with properties similar to R404A and a GWP about 45% lower

49

Medium

What distinguishes R1234yf from R134a?


A higher normal boiling point
Higher toxicity
A higher critical temperature
It is mildly flammable (class A2L), whereas R134a is non-flammable (A1)

50

Medium

How does CO₂ (R744) compare with R134a?


It has a lower critical temperature, much higher operating pressures and a much higher volumetric cooling capacity (smaller compressors and pipes)
It has identical properties and is a drop-in replacement for R134a
Unlike R134a, it is an azeotropic mixture
Its temperature glide is 7 K greater than that of R134a

51

Medium

Which of the following is NOT a fluorinated greenhouse gas?


Sulphur hexafluoride (SF6).
Hydrofluorocarbons (HFCs).
Carbon dioxide (CO₂).
Perfluorocarbons (PFCs).

52

Difficult

What additional protective equipment will you use when brazing systems containing HC refrigerants?


A flammable gas detector
A high-visibility vest
Ear defenders
Latex gloves

53

Difficult

Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?


The pressure switch setting will not be correct
It is a potential source of ignition
There is a risk of refrigerant leakage
Dust and moisture may enter

54

Difficult

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no sources of ignition?


3 m
1 m
0.5 m
2 m

55

Difficult

What is the maximum safe R32 fill of a recovery cylinder approved for flammable gas that holds 20 kg of R410A (the liquid density of R32 is about 8-10% lower)?


18 kg
20 kg
33 kg
9 kg

56

Difficult

What is the maximum charge of an A3 refrigerant for a hermetic display cabinet with an integral condenser located in the ground-floor sales area of a supermarket?


0,494 kg
1.0 kg
10 kg
2.5 kg

57

Difficult

How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?


Position the pump at least 3 m above floor level
Ignition-source-free pump, good ventilation, exhaust to a safe place
Such systems need not be evacuated before charging
Place the pump directly on the floor, as low as possible

58

Medium

What is the greenhouse effect?


Chlorine compounds destroy stratospheric ozone, increasing UV radiation at the surface
Dust in the atmosphere reflects sunlight, lowering the average surface temperature
Greenhouse gases absorb and re-emit the Earth's infrared radiation, warming the lower atmosphere
Clouds reflect ultraviolet radiation, which makes the air near the surface warmer

59

Difficult

What safety measure must you carry in your vehicle when transporting flammable refrigerant cylinders?


Thick gloves
A fire extinguisher
Tinted safety goggles
A fire blanket

60

Difficult

How would you prepare a 10 kg R32 water chiller located outdoors for debrazing its joints?


Recover the R32 to a vacuum, then fill the system with nitrogen to a slight positive pressure (approx. 0.1 bar g)
Recover the R32 to a vacuum and start desoldering immediately
Vent the R32 outdoors, then fill and vent the system with nitrogen three times
Vent the R32 outdoors and purge the system

61

Medium

What is R1270?


Propene (propylene)
Isobutane
Propane
n-Butane

62

Difficult

Which of the following leak detection methods should NOT be used to locate an HC refrigerant leak?


Leak detection foam
Electronic HFC leak detector
Electronic leak detector for flammable refrigerants
Soapy water solution

63

Difficult

What is the most important difference between a flammable refrigerant recovery unit and a standard one?


Different low-pressure switch setting
Different connection sizes
A flammable refrigerant recovery unit has no ignition sources
A different colour for the station

64

Difficult

Which of the following is a source of ignition?


A contactor (sparking contacts)
An 'n'-type (non-sparking) thermostat
An Ex-certified fan motor
A sealed NTC temperature sensor

65

Difficult

What particularly hazardous substance is formed when R32 burns?


Phosgene
Sulphur dioxide (SO₂)
Hydrogen chloride (HCl)
Hydrogen fluoride (HF)

66

Difficult

What type of refrigerant is R1234ze(E)?


CFC (chlorofluorocarbon)
HC (hydrocarbon)
HCFC (hydrochlorofluorocarbon)
HFO (hydrofluoroolefin)

67

Difficult

What hazards does a safety group A3 refrigerant pose?


Lower toxicity, moderate flammability
Higher toxicity, moderate flammability
Higher toxicity, higher flammability
Lower toxicity, higher flammability

68

Difficult

According to EN 378, what is the maximum R290 charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL of R290 = 0.038 kg/m³, access category a, location class I, no additional measures))?


1.0 kg
4.93 kg
1.5 kg
0.285 kg

69

Easy

What does the GWP indicator mean?


The ability of a substance to restore the ozone layer
The annual rise in mean air temperature caused by the emission of 1 kg of the gas
Global Warming Potential: the climate warming impact of 1 kg of a gas compared with 1 kg of CO₂ (GWP = 1) over a defined time horizon, usually 100 years
Ozone depletion potential

70

Difficult

What is the approximate ratio of the volumetric cooling capacity of R32 to that of R410A (same compressor and conditions)?


approx. 1.3
approx. 0.6
approx. 1.05–1.1
approx. 0.75

71

Difficult

Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?


Because they must be kept running continuously to disperse the leaking refrigerant
To avoid a source of ignition in the event of a flammable refrigerant leak
Because they are more reliable
Because they are more energy-efficient

72

Difficult

Why is the density difference between HC and HFC refrigerants important?


An HC charge in kg is roughly half that of an HFC
Because HCs must be charged much more slowly than HFCs
Because HCs operate at much higher pressures
Because it determines the system's energy efficiency

73

Difficult

What is the GWP of R290 according to Annex VI to Regulation (EU) 2024/573?


0.02
675
7
150

74

Difficult

Which of the following is NOT a source of ignition?


An Ex-certified fan motor
An unsealed mechanical pressure switch
An electrical switch
A light switch

75

Difficult

What is R290?


Propane
Butane
Isobutane
Propene (Propylene)

76

Difficult

What is the maximum A2L charge for a hermetic display cabinet with integral condenser in the ground-floor sales area of a supermarket?


150 g
2.5 kg
1.5 kg
1.2 kg

77

Difficult

Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?


Current consumption differs for compressors using flammable refrigerants compared to those using HFCs
It could be a source of ignition
The method of starting the compressor motor differs from that used with HFCs
A relay is never required for compressors using flammable refrigerants

78

Difficult

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no ignition sources?


10 m
3 m
5 m
1 m

79

Difficult

A recovery cylinder holds 10 kg of R404A (filling ratio 0.82 kg/l). What is the maximum R290 charge for this cylinder (propane filling ratio 0.43 kg/l per ADR P200)?


approx. 17 kg
approx. 8 kg
20 kg
approx. 5.2 kg

80

Medium

How do refrigeration systems contribute to the greenhouse effect?


Indirectly (through energy consumption) and directly (through emissions of refrigerant into the atmosphere)
Only through the heat rejected by the condenser
Through oil emitted into the atmosphere from the condenser and filter
Only through CO₂ given off by the compressor motor

81

Difficult

How can a vacuum pump be used safely to evacuate a system containing R290?


R290 systems need not be evacuated before charging
Ignition-source-free pump, good ventilation, exhaust to a safe place
Position the pump at least 3 m above floor level
Place the pump directly on the floor, as low as possible

82

Difficult

Under ADR, what equipment must you carry in your vehicle when transporting flammable refrigerant cylinders (under the 1.1.3.6 exemption)?


Tinted safety goggles
A fire blanket
A fire extinguisher (at least 2 kg dry powder)
Thick gloves

83

Difficult

How do you make sure it is safe to light the torch for desoldering joints in a system from which a flammable refrigerant has been removed?


Purge the system with compressed air
Working outdoors is sufficient
Such joints must never be desoldered; they must be cut with a pipe cutter
Ensure good ventilation and check the work area with a flammable gas detector

84

Difficult

How would you prepare a system containing 100 g of R1270 for debrazing, if local regulations allow controlled venting of small HC quantities?


Recover the R1270 to a vacuum and start brazing immediately without a nitrogen purge
Vent the R1270 outdoors and start brazing immediately
Vent the R1270 into the room and open a window
Vent the R1270 to a safe outdoor location, then purge with OFN three times (pressurise and vent), and braze with OFN flowing

85

Difficult

Which method should NOT be used to locate an R290 leak?


Leak detection foam
Fluorescent dye and UV lamp (if approved by the manufacturer)
An electronic detector for flammable refrigerants
An electronic leak detector designed for HFCs

86

Difficult

Why can’t recovery stations designed for HFCs be used with R600a?


They contain ignition sources
The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure
The recovery unit cannot withstand the working pressure of R600a
The oil in the recovery unit is not soluble in R600a

87

Difficult

According to EN 378, what is the maximum R1234ze(E) charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL = 0.303 kg/m³, access category a, location class I, no additional measures)?


2.27 kg
618 kg
6.18 kg
227 kg

88

Difficult

What type of refrigerant is R32?


Hydrocarbon
Hydrofluoroolefin
Hydrofluorocarbon
Carbon dioxide

89

Difficult

What hazards do A2L refrigerants pose?


Higher toxicity, higher flammability
Lower toxicity, higher flammability
Higher toxicity, lower flammability
Lower toxicity, lower flammability (burning velocity ≤ 10 cm/s)

90

Difficult

What hazard is associated with the combustion of HFO or HFC refrigerants?


Phosgene is formed
Nitrous oxide is formed
Hydrogen fluoride (HF) is formed
Ozone is formed

91

Medium

What is the greenhouse effect?


The trapping of heat in the Earth's atmosphere, which hinders the radiation of heat into space
The absorption of solar radiation by the Earth's surface
The formation of a layer that traps only heat from fuel combustion in aircraft
The filtering of solar radiation by the atmosphere

92

Difficult

Approximately what compressor displacement is required for R600a compared with R134a for the same cooling capacity?


About seven times as large
The same
About twice as large
About half

93

Difficult

What is the GWP value for R32 according to Regulation (EU) 2024/573?


0
7
675
3

94

Difficult

Why is charge accuracy more important in critically charged R290 systems than in HFC systems?


Because such systems never have liquid receivers
Because of lower operating pressures
Because R290 is only used in systems below 150 g
The charge mass is much smaller than in an HFC system, because the liquid density of R290 is much lower

95

Difficult

Why does the condenser fan run continuously in some systems using R1270?


To reduce energy consumption
To dilute the refrigerant in the event of a leak
To ensure that the discharge pressure never becomes excessive
To prevent the build-up of contaminants in the condenser

96

Medium

Which EU regulation is currently the primary piece of legislation governing the use of fluorinated greenhouse gases (F-gases) in the European Union?


Regulation (EU) 2015/1188
Regulation (EU) No 517/2014
Directive 2009/125/EC
Regulation (EU) 2024/573

97

Medium

What is the main objective of Regulation (EU) 2024/573?


To reduce taxes on refrigeration equipment
Prevention of F-gas emissions and the achievement of the EU’s climate targets
To facilitate the import of electrical appliances
Standardising metal recycling standards

98

Medium

What are the ecodesign obligations of manufacturers of refrigerating appliances?


Only declaring F-gas quantities under Regulation (EU) No 517/2014
Only using energy labels under Regulation (EU) 2024/573
Only implementing an ISO 9001 quality management system
Meeting implementing regulations (e.g. 2019/2019, 2015/1095): efficiency, spare parts, reparability

99

Medium

What is the main objective of EU ecodesign legislation (Directive 2009/125/EC, now Regulation (EU) 2024/1781 – ESPR)?


To reduce the negative environmental impact of products by improving energy efficiency, durability and recyclability
To standardise the appearance of products in the EU
To facilitate imports from outside the EU
To increase sales of electrical appliances in the EU

100

Medium

What is the function of a ball valve in a refrigeration system?


Enables the refrigerant flow to be completely shut off
It prevents excessive pressure build-up in the system
It regulates the temperature of the refrigerant
It measures the moisture content of the refrigerant

101

Easy

What is the main function of a safety valve?


Prevents the evaporator from freezing
It monitors the moisture content of the refrigerant
Discharges refrigerant when the set pressure is exceeded
It controls the oil level in the compressor

102

Medium

How do certain gases contribute to the greenhouse effect?


They trap thermal radiation that the Earth would otherwise emit into space
They limit UV radiation reaching the Earth's surface, changing the heat balance
They heat the air through chemical reactions with atmospheric oxygen and nitrogen
They deplete the ozone layer, so more solar radiation reaches the surface

103

Medium

What is the purpose of a sight glass (with moisture indicator)?


Regulating compressor pressure
Visual assessment of the refrigerant condition in the liquid line (bubbles) and of system moisture
Emergency shut-off of flow
Measuring condenser temperature

104

Medium

What is the function of the temperature regulator in a refrigeration system?


It drains excess refrigerant into the receiver
It restricts oil flow
Controls the operation of the compressor and valves to maintain the set temperature
To maintain a constant pressure in the compressor

105

Difficult

What is the role of a suction liquid separator (also in systems with flammable or toxic refrigerants)?


It heats the refrigerant before the evaporator
It separates liquid from oil
It prevents liquid refrigerant from entering the compressor
It is used only to measure moisture

106

Difficult

What is the function of an oil separator in systems using flammable or toxic refrigerants?


They are used solely to measure the moisture content of the refrigerant
Separates oil from the refrigerant and facilitates the return of oil to the compressor
Heats the refrigerant before it enters the evaporator
It prevents liquid from entering the compressor

107

Medium

What is the purpose of oil level regulators in a refrigeration system?


They control the pressure in the condenser
They drain off excess refrigerant
They control the evaporator temperature
Maintains the correct oil level in the compressor

108

Medium

What is the function of the liquid receiver in relation to system tightness?


It keeps the whole system at constant pressure regardless of load
It regulates the oil returning to the compressor
It stores refrigerant; checking its liquid level helps detect charge loss
It controls the evaporating temperature by varying the circulating charge

109

Medium

What is the role of a gauge manifold with thermometers (temperature probes)?


It measures pressures and temperatures to determine superheat and subcooling and thus assess the system charge (indirect leak check)
It relieves pressure if it is exceeded
It monitors refrigerant moisture content
It controls oil level

110

Medium

What is the role of defrost controls?


They drain excess oil from the evaporator to the receiver
They monitor the moisture content of the refrigerant
They protect the evaporator from icing and damage that could lead to leaks
They control compressor discharge pressure during defrost

111

Difficult

Why do liquid and oil separators in CO₂ systems require particular attention?


Because of very high pressures – adequate PS and protection devices are required
Because sight glasses and level indicators must not be used in CO₂ systems
Because CO₂ is flammable and separators must not be used
Because CO₂ needs no lubrication, so oil separators are unnecessary

112

Difficult

What is the critical pressure of CO₂ (R744)?


Approx. 10 bar
Approx. 31 bar
Approx. 74 bar (abs)
Approx. 120 bar

113

Easy

What is the unit of pressure in the International System of Units (SI)?


atm (standard atmosphere)
psi (pound per square inch)
bar (gauge)
Pa (pascal)

114

Medium

Where can the lists of fluorinated greenhouse gases be found?


In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases
In a regulation of the Minister of Economy on the list of fluorinated greenhouse gases
In Annexes I–III to Regulation (EU) 2024/573 of the European Parliament and of the Council
In the Vienna Convention for the Protection of the Ozone Layer

115

Difficult

What characterises the transcritical process in CO₂ systems?


It occurs only at low temperatures
Heat rejection takes place above the critical point – the refrigerant does not condense in the conventional way (gas cooler instead of condenser)
Conventional condensation occurs
It is irrelevant to system operation

116

Difficult

What characterises the subcritical CO₂ process?


The absence of condensation
The absence of evaporation
The conventional condensation process below the critical point
Operation above the critical point

117

Easy

What is the log(p)-h diagram for CO₂ used for?


For analysing thermodynamic processes in a refrigeration system
To detect leaks
To regulate pressure
To measure temperature

118

Easy

What can be read from the log(p)-h graph?


Only the humidity
Only the amount of refrigerant
Pressure, enthalpy, temperature and state of the refrigerant
Only the temperature

119

Easy

What are CO₂ saturation tables used for?


To regulate the compressor
To measure humidity
To determine the oil quantity
To determine the relationship between temperature and pressure at saturation

120

Easy

What does the CO₂ saturation state mean?


A state of high pressure
A state in which the refrigerant is only a gas
Equilibrium between the liquid and vapour phases
Dry ice state

121

Difficult

When can dry ice (solid CO₂) form?


During normal operation of the system
At high temperature
At high pressure
When the pressure drops suddenly below the triple point (approx. 5.2 bar abs, −56.6 °C), e.g. when venting liquid CO₂ or charging liquid into an evacuated system

122

Difficult

What risks are associated with dry ice forming in a CO₂ system?


Improved efficiency
No risk
Blocked pipes and valves and system damage (and a sharp pressure rise when it thaws)
Pressure reduction

123

Difficult

How does CO₂ saturation pressure change as temperature increases?


It increases rapidly
It remains the same
It first decreases, then increases
It decreases

124

Easy

Why is understanding the log(p)-h graph particularly important for CO₂?


As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It doesn’t matter
It is only used for design purposes
It only applies to NH₃

125

Medium

Where can the lists of ozone-depleting substances be found?


In Annexes I and II to Regulation (EU) 2024/590 of the European Parliament and of the Council
In the Vienna Convention for the Protection of the Ozone Layer
In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases
In a regulation of the Minister of the Environment on the list of controlled substances

126

Difficult

What happens to CO₂ above the critical point?


It transitions to a supercritical state (no distinction between liquid and gas)
It turns into a liquid
It ceases to conduct heat
It turns into a solid

127

Easy

Why do CO₂ systems require precise pressure control?


Because there are no valves
Due to low pressures
Due to significant pressure changes with temperature fluctuations
They do not require control

128

Medium

Why is ammonia (R717) classed as a toxic refrigerant?


Because it is heavier than air and displaces oxygen
It severely irritates the respiratory tract, eyes and skin, and is poisonous when inhaled at higher concentrations
Because it does not react with water, making neutralisation difficult
Because it is colourless and odourless and therefore hard to detect

129

Difficult

What is the main difference between a dry-expansion and a flooded evaporator?


A dry-expansion evaporator is filled with liquid, a flooded one with vapour
A dry-expansion evaporator needs no expansion valve, a flooded one does
A dry-expansion evaporator always has a lower pressure than a flooded one
In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)

130

Difficult

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Positive pressure of 5–10 bar
Positive pressure of 10–20 bar
Atmospheric pressure, approx. 1 bar abs
Below atmospheric (approx. 0.7 bar abs at −40 °C)

131

Difficult

Why are PFAS formed by the decomposition of certain F-gases (e.g. TFA from HFOs) problematic?


They are readily biodegradable
They are climate- and environment-neutral
They are very persistent, accumulate in the environment (e.g. water) and may be toxic
They cause rapid cooling of the atmosphere

132

Easy

What is the basic requirement when charging a system with R717 (NH₃)?


Charging must only take place at temperatures below 0°C
Charging can be carried out without personal protective equipment
Charging should take place in a well-ventilated area using appropriate personal protective equipment
NH₃ can be charged together with air

133

Difficult

How is oil managed in R717 systems?


Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer
Oil has no effect on system operation
Oil can be mixed with any refrigerant
Oil requires no monitoring

134

Easy

What is the correct procedure for recovering R717 from a system?


The gas can be released into the atmosphere
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
Recovery is not required
The refrigerant can be drained into the sewer system

135

Easy

How should R717 (NH₃) be stored?


In any open containers
In unmarked plastic containers
Near heat sources
In sealed, labelled containers, in a cool and well-ventilated place

136

Medium

Where and by when must entities obliged under the Polish Act of 15 May 2015 submit annual reports on ODS and F-gases?


By 28 February of the following year, electronically via the Reports Database (BDS) run at the Institute of Industrial Chemistry (ICHP)
By the end of the calendar year, on a form at a regional office of the Office of Technical Inspection (UDT)
By 31 March, electronically to the Ministry of Climate and Environment
By 31 January, in the Central Register of Operators (CRO)

137

Difficult

What should be done with contaminated R717?


Continue to use it without restriction
Dilute it with water and reuse it
Release it into the atmosphere
Purify it or send it for disposal in accordance with regulations

138

Easy

What is the main hazard associated with an R717 leak during maintenance work?


Increased cooling efficiency
Damage to electrical equipment only
No risk whatsoever
Toxic to humans and may cause chemical burns

139

Difficult

What should be done if an NH₃ leak is detected?


Increase the pressure in the system
Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)
Carry on working wearing a dust mask
Carry on working with the room door open

140

Difficult

What role do scrubbers play in NH₃ systems?


They store the refrigerant
They increase the pressure in the system
They are used to measure temperature
Neutralise ammonia through absorption in a liquid (e.g. water)

141

Difficult

How should the system be prepared before filling with R717?


There is no need to check it
The pressure must be increased above the standard level
Simply start it up
Check for leaks, remove air and moisture, and create a vacuum

142

Difficult

What are the transport requirements for R717?


It can be carried without labelling
It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)
It can be carried in open containers
Transport is not regulated

143

Easy

What personal protective equipment is required when working with NH₃?


Safety goggles, gloves and respiratory protective equipment
Only a safety helmet
No requirements
Workwear only

144

Medium

Which installation measure has a major impact on compressor energy efficiency?


Installing a suction line smaller than recommended
Charging extra refrigerant 'as a reserve' above the nameplate value
Omitting the filter-drier to reduce flow resistance
Proper evacuation and dehydration of the system (removing air and moisture)

145

Medium

How does regular oil-level monitoring affect compressor operation?


It allows any type of oil to be topped up
It increases cooling capacity above nominal
It allows the crankcase heater to be omitted
It ensures proper lubrication and limits wear and energy losses

146

Easy

How do system leaks affect compressor energy efficiency?


No effect as long as the system still cools
Refrigerant loss reduces capacity and increases energy use (longer run times, higher superheat)
They affect only safety, not energy use
They improve efficiency because condensing pressure drops

147

Medium

Regulation (EU) 2024/590 relates to:


Conditions for F-gas certification of companies recovering and reclaiming refrigerants
Alternative refrigerants replacing fluorinated greenhouse gases
Health and safety during refrigerant recovery
Ozone-depleting substances

148

Medium

What is the significance of proper suction and discharge pressure control?


Pressures do not affect energy use
The lowest possible suction pressure is best
It keeps the compressor at optimal conditions (suction pressure as high and condensing pressure as low as permissible)
The highest possible condensing pressure is best

149

Medium

Which maintenance measure reduces compressor energy consumption?


Replacing the filter-drier when the pressure drop or moisture indicator shows it is necessary
Permanently disabling the crankcase heater
Topping up refrigerant at every service visit
Raising the high-pressure switch setting

150

Medium

How does air (non-condensable gas) in the system affect operation?


It lowers the condensing pressure
It improves condenser heat transfer
It raises the condensing pressure and reduces efficiency
It only affects the sight-glass indication

151

Medium

What role do controls play in compressor efficiency?


They enable optimised operation and lower energy use (e.g. floating head pressure, capacity matching)
They matter only in NH₃ systems
They increase the circulating refrigerant charge
They provide safety only, with no energy effect

152

Medium

How does suction superheat at the compressor affect efficiency?


Zero suction superheat is optimal
The higher the superheat, the higher the efficiency
Superheat has no effect
Excessive superheat reduces efficiency and raises the discharge temperature

153

Medium

How does correct system layout affect efficiency?


It affects only appearance
It shortens pipe runs and limits pressure drops and energy losses
Longer pipes improve subcooling and always increase efficiency
It doesn't matter

154

Medium

How important is suction pipe insulation?


It has no effect
It increases energy consumption
It is needed only for appearance
It limits heat gain and excessive superheat, improving efficiency

155

Medium

Which measure most improves condenser energy efficiency?


Raising the condensing pressure set point
Increasing the refrigerant charge
Reducing fan speed to the minimum
Regular cleaning of heat-exchange surfaces

156

Easy

How does a dirty condenser affect the operation of the refrigeration system?


It lowers the condensing pressure
Causes an increase in pressure and energy consumption by the compressor
It has no effect
It improves efficiency

157

Easy

Why is adequate airflow through an air-cooled condenser important?


It doesn't matter
It ensures effective heat rejection and low condensing pressure
It affects only noise
The lower the airflow, the lower the condensing pressure

158

Medium

Which refrigerants damage the ozone layer?


All refrigerants containing carbon in their molecules
All refrigerants containing fluorine and hydrogen in their molecules
All natural refrigerants
All refrigerants containing chlorine or bromine in their molecules

159

Easy

How does the presence of limescale in a water-cooled condenser affect performance?


It lowers the condensation temperature
It improves heat transfer
Impairs heat exchange and increases energy consumption
It has no effect

160

Medium

How does correct condensing pressure control affect efficiency?


It has no effect
It keeps the lowest pressure that still ensures proper expansion-valve feed, reducing energy use
It is best to keep a constant high condensing pressure all year
It always increases energy use

161

Easy

How do condenser leaks affect energy efficiency?


Have no effect
They lower the temperature
They improve efficiency
Causes refrigerant loss and a drop in efficiency

162

Easy

How important is the correct positioning of an air-cooled condenser?


It doesn’t matter
It should be installed in a well-ventilated area with unobstructed airflow
It should be close to heat sources
It should be housed in a small room

163

Easy

How does hot air recirculation affect the condenser?


It improves efficiency
It has no effect
It reduces the pressure
Impairs cooling and increases energy consumption

164

Medium

How does insulation of heating and DHW pipework affect the efficiency of a heat pump system?


It doesn't matter
It impairs cooling
It reduces energy losses and improves overall system efficiency
It increases pressure

165

Medium

Which measure most improves the energy efficiency of an air-cooling evaporator?


Raising the condensing temperature by a few kelvin
Restricting the airflow through the evaporator
Increasing the refrigerant charge above nominal
Defrosting at the right time and keeping the fins clean

166

Easy

How does evaporator icing affect the system’s operation?


It lowers the condensation temperature
It improves cooling performance
Impairs heat exchange and increases energy consumption
It has no effect

167

Easy

How does dirt on the evaporator surface affect its performance?


It improves efficiency
Impairs heat exchange and increases energy consumption
It reduces the pressure
It has no effect

168

Easy

What maintenance task is crucial for the evaporator?


Reduced airflow
Lack of maintenance
Increasing the refrigerant charge
Regular cleaning and defrosting

169

Medium

What does a Certificate A2 for natural persons (Implementing Regulation (EU) 2024/2215) authorise?


All activities (leak checks, installation, repair, maintenance, servicing, decommissioning, recovery) involving F-gases and hydrocarbons in equipment containing less than 3 kg, or less than 6 kg in labelled hermetically sealed systems
Only recovery of F-gases from equipment containing less than 3 kg (or 6 kg in hermetically sealed systems)
Only leak checks that do not entail breaking into the refrigerant circuit
All activities involving equipment using CO₂ (R744)

170

Easy

How does superheat at the evaporator outlet affect efficiency?


It only causes a temperature drop
It has no effect
Excessive superheat reduces energy efficiency
It always improves performance

171

Easy

How do leaks in the evaporator affect efficiency?


Have no effect
These cause refrigerant loss and a drop in efficiency
Improves performance
Increase capacity

172

Easy

How important is correct expansion valve adjustment?


Ensures optimal evaporator charge and improves efficiency
It increases energy consumption
Causes leaks
It doesn’t matter

173

Easy

How does inadequate insulation of suction (or secondary-coolant) pipes affect evaporator performance?


It improves efficiency
It lowers the condensing temperature
It causes cooling losses and increased energy use
It has no effect

174

Easy

How does correct TEV adjustment affect system energy efficiency?


It increases energy use
It ensures optimal superheat and improves efficiency
It has no effect
It causes leaks

175

Easy

What happens if the superheat set by the TEV is too high?


The refrigerant charge will increase
Cooling efficiency will improve
Efficiency will drop because the evaporator is not being fully utilised
It has no effect

176

Medium

How does too low superheat setting on the TEV affect performance?


It may lead to improved efficiency, but it increases the risk of the compressor becoming flooded with liquid
It reduces refrigerant flow
It increases operational safety
It has no effect

177

Easy

How do contaminants in the system affect the operation of the TEV?


They lower the temperature
Have no effect
They improve its performance
They can cause it to become blocked and reduce efficiency

178

Easy

What role does the filter-drier play in terms of system efficiency?


It increases the amount of refrigerant
Removes moisture and contaminants, improving the system’s efficiency
It lowers the temperature
It doesn’t matter

179

Easy

How does proper insulation of components (e.g. pipes near the TEV) affect the system?


It doesn’t matter
Prevents unwanted heat gains and improves efficiency
It increases energy consumption
It causes leaks

180

Medium

What is the scope of Regulation (EU) 2024/573?


Limiting emissions, use and marketing of F-gases, HFC phase-down, certification and reporting
Health and safety requirements for brazing and welding on refrigeration installations
Design requirements and conformity assessment for pressure equipment
Only requirements for periodic leak checks of refrigeration equipment

181

Easy

How important is it to check the operation of the condensing pressure control valve in the system?


Ensures operation within the optimum pressure range and reduces energy losses
It causes a significant rise in temperature
It increases energy consumption
It has no effect

182

Easy

How does the correct selection of a TEV affect energy efficiency?


Ensures the system is matched to its capacity and operates optimally
It increases the amount of refrigerant
It lowers the temperature
It doesn’t matter

183

Medium

What is the main design difference in hydrocarbon refrigeration systems?


The need to eliminate ignition sources and limit the charge because of the refrigerant's flammability
No need for safety measures
Lower energy efficiency
Higher operating pressures

184

Medium

How do compressors used in hydrocarbon systems differ?


They need no lubrication
They must operate at higher pressures than HFC compressors
There is no difference
They must be approved by the manufacturer for the specific flammable refrigerant (e.g. electrical components that are not ignition sources, suitable oil)

185

Difficult

What is the main characteristic of R744 (CO₂) refrigeration systems?


Low operating pressures
No need for control
Low energy efficiency under all conditions
Very high operating pressures

186

Difficult

What are the requirements for piping materials in CO₂ systems?


They must withstand high pressures (e.g. stainless steel, high-strength copper-alloy tubes such as K65)
Any material may be used
Only plastics
It doesn't matter

187

Difficult

How does a booster system work in CO₂ installations?


Low-temperature (LT) compressors discharge into the suction of medium-temperature (MT) compressors – two-stage compression in a single circuit
It reduces evaporator pressure
It is used to store refrigerant
It reduces the refrigerant quantity

188

Easy

What is the function of high-pressure control valves in CO₂ systems?


They lower the evaporator temperature
They are used to store the refrigerant
They regulate oil flow
They control the pressure on the high-pressure side and optimise system operation

189

Difficult

Why is pressure optimisation in CO₂ systems crucial?


It reduces the ambient temperature
It reduces the amount of refrigerant
It enables the system to achieve maximum energy efficiency in transcritical mode
It doesn’t matter

190

Difficult

What role does parallel compression play in CO₂ systems?


It increases energy consumption
It lowers the ambient temperature
It compresses flash gas from the intermediate receiver directly to high pressure, improving efficiency
It has no significance

191

Medium

How can you tell that the system has been overcharged with refrigerant?


The compressor runs at a lower load and the suction pressure drops
Under normal operating conditions the condensing pressure and subcooling rise markedly because excess liquid floods the condenser and reduces its active surface
Even under a very small heat load, frost forms on the suction line
It cannot be checked, because the sight glass is not intended for this

192

Difficult

How does an ejector work in a CO₂ system?


Stores the refrigerant
It increases the amount of refrigerant
It lowers the evaporator temperature
It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency

193

Difficult

What is the function of liquid ejectors in CO₂ systems?


They return liquid from the separator and allow partially flooded evaporator operation (better evaporator feed)
They reduce atmospheric pressure
They increase the amount of oil
They raise the refrigerant temperature

194

Difficult

What are the characteristics of partially flooded systems in CO₂ systems?


The absence of liquid in the evaporator
The presence of liquid in the evaporator, which improves heat transfer and efficiency
Lack of regulation
Low operating pressure

195

Difficult

What is the main risk associated with standstill pressure in CO₂ systems?


A decrease in refrigerant quantity
A pressure rise as the refrigerant warms up during standstill (possibly exceeding PS and lifting the relief valves)
Increased efficiency
A drop in temperature

196

Difficult

How is standstill pressure limited in CO₂ systems?


By completely shutting down the system and power supply
By increasing the refrigerant charge
By raising the plant-room temperature
By using an auxiliary standstill (stagnation) cooling unit, e.g. cooling the receiver, with back-up power, and by selecting an adequate PS and relief valves

197

Difficult

What does standstill (stagnation) of a CO₂ system mean, and why is it important?


A drop in system temperature
A state with no compressor operation or refrigerant flow – pressure rises with ambient temperature and may exceed PS
Improved efficiency
Normal system operation

198

Easy

Why do CO₂ systems require more advanced automation than traditional systems?


Because there are no valves
Due to the need for precise control of pressure and temperature
They do not require automation
Due to low pressures

199

Difficult

What must the label of a flammable refrigerant cylinder include?


The refrigerant name, the UN number, the hazard label (e.g. 2.1 – flammable gas) and basic safety information
Only the net weight
Only the refrigerant name
Information about the cylinder owner

200

Difficult

Why is the absence of a 'flammable refrigerant' label on equipment a serious hazard?


It may lead to the wrong oil being selected
It has no significant effect on safety
It may lead to the use of tools that are ignition sources
It reduces system efficiency

201

Difficult

Which set of information on the label of a flammable refrigerant cylinder is crucial from a safety perspective?


Name of the substance, hazard label (ADR) / GHS pictogram (CLP), UN number
Cylinder colour and date of manufacture
Manufacturer’s name and country of origin
Gross weight and batch number

202

Medium

Before charging the unit with refrigerant, it is essential to…


…carry out a tightness test (and evacuate the system)
…fill in the unit's data sheet
…check the compressor suction and discharge connections
…carry out a trial start-up

203

Easy

What is the requirement regarding the labelling of an installation containing a flammable substance?


Labelling is not required for hermetically sealed systems
The labelling must indicate the type of substance and the flammability hazard
Labelling is required only in technical rooms
Colour-coding of pipes is sufficient

204

Easy

What are the potential consequences of using unsuitable connections in a system containing a flammable substance?


No impact on safety
Risk of leakage and the formation of an explosive mixture
Merely installation difficulties
Merely a reduction in efficiency

205

Difficult

What is the purpose of gas detectors in a room with a refrigeration system?


Monitoring pipe pressure
Early leak detection and triggering of measures preventing health risks and explosive atmospheres (alarm, ventilation, shut-off)
Measuring refrigerant temperature
Controlling compressor capacity

206

Difficult

How often should gas detection sensors in a machinery room be checked?


Once every 5 years
Only after a leak has occurred
Before every start-up of the unit
According to the manufacturer's instructions and regulations – at least every 12 months

207

Difficult

Where should a gas detector be located according to EN 378?


Anywhere in the room
Only at the room entrance
Where the refrigerant would accumulate: low (near the floor) for refrigerants heavier than air, high (near the ceiling) for lighter ones such as NH₃
Near the control panel

208

Easy

How should an employee respond when a gas alarm is triggered?


Reduce the pressure in the system
Switch off the system and wait for the alarm to stop
Leave the room immediately and notify their supervisor
Carry on working until they see a leak

209

Difficult

What safety checks should be carried out when installing a new refrigeration system with a flammable refrigerant?


The presence of health and safety signage, adequate ventilation and gas detectors
The colour of pipes and hoses
Only the compressor power
Only that the air filter is new

210

Easy

Gas detectors should be installed in rooms where:


Any refrigerant is present, regardless of the quantity
The room is less than 5 m²
The amount of refrigerant exceeds a specified permissible threshold
Ventilation is natural

211

Difficult

What are the requirements for emergency exits from a refrigeration machinery room?


At least two exits are required and signage is optional
In small machinery rooms emergency exits need not be signed
One exit with a sign stating the refrigerant type is sufficient
Outward-opening doors and signed escape routes (number of exits per the standard)

212

Difficult

Which installation measure for a flammable-refrigerant system improves its energy efficiency?


Omitting the filter-drier
Restricting room ventilation
Charging above the nameplate quantity
A thorough tightness test and evacuation (dehydration) of the system

213

Medium

What information must appear on the label of equipment containing F-gases?


That it contains an F-gas, its designation, quantity in kg and t CO₂ eq, and GWP
Only the trade name of the refrigerant and the unit's serial number
The weight and capacity of the pipework and the colour code of the casing paint
The manufacturer's logo, the unit weight and year of manufacture from the rating plate

214

Easy

How do leaks affect systems using flammable refrigerants?


They lower the temperature
They improve efficiency
They cause refrigerant loss, reduced efficiency and a fire hazard
Have no effect

215

Difficult

Why is it important to limit the refrigerant charge in HC systems?


It lowers the temperature
It doesn't matter
It increases capacity
It limits the possibility of reaching a flammable concentration (≥ LFL) in a leak, increasing safety

216

Easy

Why is the cleanliness of heat exchangers in HC systems important?


It improves heat transfer and reduces energy consumption
It doesn’t matter
It increases the pressure
Causes leaks

217

Easy

What maintenance measures improve the efficiency of a system using a flammable refrigerant?


Increasing the refrigerant charge
Lack of servicing
Disabling safety devices
Regular checks for leaks and operating parameters

218

Easy

How does the correct selection of components affect a system using a flammable refrigerant?


It ensures safe and optimal operation and minimises energy losses
It increases the amount of refrigerant
It lowers the temperature
It doesn’t matter

219

Easy

Why is it important to use the correct service tools in HC systems?


It ensures operational safety and reduces refrigerant losses
It doesn’t matter
Causes leaks
It increases energy consumption

220

Easy

How does pipe insulation affect the efficiency of systems containing HC?


Causes leaks
It reduces energy losses and improves efficiency
It doesn’t matter
It increases the pressure

221

Difficult

Which safety class applies to R744?


B2L
A2.
A1
A3

222

Difficult

In a simple single-stage R744 system without an intermediate receiver (refrigerant flows from the gas cooler directly to the expansion valve), operating transcritically at 90 bar with a gas-cooler outlet temperature of 35 °C, the refrigerant upstream of the expansion valve is…


…a subcooled liquid
…a two-phase mixture at intermediate pressure
…saturated vapour at intermediate pressure
…a supercritical fluid

223

Difficult

In R744 transcritical systems, the gas cooler outlet valve controls:


The inlet temperature to the gas cooler
The pressure in the gas cooler
The gas cooler fans
The outlet temperature of the gas cooler

224

Easy

What is the base unit of temperature according to the International System of Units (Système International d’Unités)?


K
°R
°C
°F

225

Medium

Which set of information best reflects the content of the equipment records required by Regulation (EU) 2024/573?


Operator details, equipment details, type and quantity of refrigerant, and information on servicing and repairs
The owner, installer and service technician of the unit
The make and model of the unit
Only the date of installation and the installer's name

226

Difficult

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 does not mix with the oil; the oil collects on the high-pressure side above the R717
R717 mixes very well with the oil, which easily returns to the compressor
An oil return line cannot be used in R717 systems because the oil is too hot
R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)

227

Difficult

What is the main reason for using K65 copper tubing in some R744 systems?


They have good low-temperature performance
They bend easily
They can withstand higher pressures
They come in a wider range of diameters

228

Difficult

Which statement about installing Schrader valves is correct?


Hydrocarbons leak through Schrader valves
When brazing the valve body, the core must be removed, then refitted and tightened to the correct torque
Schrader valves must not be used in R744 systems
All Schrader cores are suitable for all refrigerants

229

Difficult

Which refrigerant can be detected with phenolphthalein paper?


R1270
R717
R744
R1234ze(E)

230

Difficult

How does an undercharge affect the high-pressure side (without discharge pressure control)?


Discharge (condensing) pressure and subcooling will both be lower
Discharge pressure lower, subcooling higher
Discharge pressure higher, subcooling higher
Discharge pressure higher, subcooling lower

231

Difficult

What is the benefit of adding helium as a tracer gas to nitrogen in a pressure test?


It has a distinctive odour that helps locate the leak
It reacts with refrigerant residues, producing a visible colour change
Its small atoms pass easily through leaks and are detected
It has a higher pressure than pure nitrogen in the same cylinder

232

Difficult

Why should an evacuated R744 system initially be charged with refrigerant in the vapour phase?


To charge R744 more slowly and measure it more accurately
To prevent the drain valve on the receiver from opening
To avoid damaging the compressor with liquid CO₂
To prevent dry ice forming (until approx. 5.2 bar abs is exceeded)

233

Difficult

If moisture remains in an R744 system because it was not properly evacuated (dehydrated), what is the likely consequence?


Excessive discharge pressure
Formation of carbonic acid, which damages the system
Reduced cooling capacity
Formation of hydrogen fluoride and hydrofluoric acid

234

Difficult

Which system may require manual oil recovery?


Supercritical ‘booster’ system using R744
Secondary system using R744
R744 cascade system
An R717 system

235

Difficult

The pressure of R744 at a saturation temperature of 20 °C is approx.


25 bar g
90 bar g
14 bar g
56 bar g

236

Medium

Who is responsible for keeping the equipment records?


The operator of the unit or system.
There is no such obligation.
The equipment maintenance technician.
The person responsible for risk assessment.

237

Difficult

Which refrigerant is lighter than air?


R717
R1234ze(E)
R1270
R744

238

Difficult

What hazards are associated with a safety group A3 refrigerant?


Lower flammability, lower toxicity
Higher flammability, lower toxicity
Lower toxicity, no flame propagation
Higher toxicity, no flame propagation

239

Difficult

What is the GWP of R32 (per AR4, as used in Regulation (EU) 2024/573)?


675
0
6
3922

240

Difficult

What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?


Lower flammability limit, room volume
Practical limit, room volume
Lower flammability limit, height of the indoor unit, floor area
Practical limit, height of the indoor unit, floor area

241

Difficult

What compressor displacement is required for R1270 compared with an R404A compressor in the medium-temperature range (cold room)?


About 6 times larger
About 1.5 times larger
Similar
About half

242

Difficult

At an ambient temperature of 25 °C, the standstill pressure in the low-pressure stage of an R744 cascade (without standstill cooling) will typically be…


…the same as the relief valve set pressure
…approx. 27.5 bar g
…higher than the maximum allowable pressure (PS) of the low-pressure stage
…the same as the high-pressure switch setting

243

Difficult

What is the correct definition of critical temperature?


The temperature above which there are no distinct liquid and gaseous phases
The temperature at which a substance changes from a gaseous to a solid state
The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid
The temperature at which, for certain substances, electrical resistance is zero

244

Difficult

In the gas cooler of a transcritical system, the supercritical working fluid…


…rejects heat during a phase change
…rejects heat as its temperature falls
…rejects heat at constant temperature and pressure
…rejects heat as its pressure falls

245

Difficult

R717 is highly corrosive to:


copper (and its alloys)
stainless steel
titanium
aluminium

246

Difficult

What can be the effect of a relief valve lifting repeatedly?


The valve stays fully open permanently
The valve no longer opens
The set pressure increases
The valve may not reseat tightly and its set (opening) pressure may decrease

247

Medium

Where are oil traps installed on the suction line?


Before the safety valve on the suction side
At the inlet to every component of the refrigeration system
Immediately before the compressor suction connection
At the bottom of vertical suction risers with upward flow

248

Difficult

What is the relationship between the pressure (p) and temperature (T) of nitrogen at the start (1) and end (2) of a tightness test (p absolute, T in kelvin)?


p₂ = (p₁ × T₁)/T₂
p₂ = T₂/(p₁ × T₁)
p₂ = (p₁ × T₂)/T₁
p₂ = T₁/(p₁ × T₂)

249

Difficult

What is the recommended pre-alarm level for fixed leak detection systems for R717?


50,000 ppm
500 ppm
500,000 ppm
5,000 ppm

250

Difficult

Why are compressors with a separate motor (open type) mostly used in R717 systems?


Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used
To increase the refrigerant charge
To lower the condensing pressure
Because they are cheaper

251

Difficult

Which type of compressor is most commonly used in large ammonia systems?


Diaphragm compressor
A reciprocating or screw compressor
Rotary vane compressor
Hermetic scroll

252

Difficult

How is the capacity of a piston compressor regulated in NH₃ systems?


By unloading the cylinders or changing the rotational speed
Solely by adjusting the oil volume
By reducing the refrigerant charge
By increasing the condensing pressure

253

Difficult

How is the capacity of a screw compressor most commonly controlled?


By changing the type of oil
By closing the suction valve
By using a slide valve
By adjusting the oil level

254

Difficult

When is two-stage compression used in NH₃ systems?


At small temperature differences
Only with water-cooled condensers
Only in small systems
At low evaporating temperatures (pressures) and high pressure ratios

255

Difficult

What is the advantage of two-stage compression over single-stage compression?


Higher energy consumption
Higher efficiency and lower discharge temperature
Lower efficiency
No need for a separator

256

Difficult

How does an evaporative condenser used in NH₃ systems work?


It transfers heat only to the air
Operates without a fan
It does not require a water supply
It utilises the evaporation of water to increase cooling efficiency

257

Difficult

What is the function of the liquid separator in an NH₃ system?


It separates oil from the refrigerant
It prevents liquid from entering the compressor
Regulates the condensing pressure
Increases the discharge temperature

258

Medium

Which symptoms with the compressor running indicate a refrigerant leak (undercharge)?


Rising condensing and suction pressures with no superheat
Sight glass full of liquid and rising oil level in the crankcase
Low suction pressure, high superheat and negligible subcooling
Rising liquid level in the receiver and increasing subcooling

259

Difficult

What is the purpose of monitoring the liquid level in the separator?


To increase the oil volume
To reduce the condensing temperature
To maintain the correct refrigerant level and prevent the compressor from flooding
To control the condenser fan

260

Difficult

What is the role of the float switch in NH₃ systems?


It is used to detect leaks
It controls the fan’s operation
It monitors the liquid level in the tank or separator
It regulates the condensation temperature

261

Difficult

What is a thermosyphon in NH₃ systems?


A type of safety valve
A defrosting device
A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling
An oil circulation pump

262

Difficult

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To increase the amount of refrigerant
Because the oil mixes only with water
Because NH₃ does not mix with most compressor oils
To reduce the pressure

263

Difficult

What is the main function of an oil separator in NH₃ systems?


Removing moisture from the system
To lower the condensation temperature
To separate the oil from the refrigerant and return the oil to the compressor
To increase fan efficiency

264

Difficult

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


A pumped liquid-recirculation system
A direct-expansion (DX) system
A glycol system
An indirect system

265

Difficult

What is the characteristic feature of a flooded evaporator system?


The evaporator contains a large amount of liquid, which improves heat transfer
No separator is used
No level control is required
The evaporator is filled exclusively with vapour

266

Difficult

What is the main difference between a direct and an indirect system?


In an indirect system, no compressor is used
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In a direct system, there is no evaporator
In an indirect system, NH₃ flows directly into the space being cooled

267

Medium

Which components of a refrigeration system are potential leak points subject to leak checks?


Only suction-side components
Joints, valves (including stems), seals (including those on replaceable filters and driers), parts subject to vibration and connections to safety and measuring devices
Hermetic compressors, liquid receivers and liquid separators
Only high-pressure-side components

268

Medium

What pressure is used for the pressure tightness test of an installation?


Always 30 bar
A pressure chosen by the technician based on experience
A pressure equal to the maximum pressure measured during operation
The pressure specified in EN 378-2 or by the manufacturer, not exceeding the maximum allowable pressure of the system (PS)

269

Medium

At which points of the unit must the leak check be carried out?


Only at connections of measuring instruments
Only on discharge-side components
Only on compressor shut-off valves, solenoid valves and filters
At all points where there is a potential risk of refrigerant leakage

270

Medium

When can a unit be considered tight after a pressure test?


When the pressure remains constant during the test (allowing for temperature-related changes); any unexplained pressure drop requires the leak to be located
When the pressure drop does not exceed 0.1 bar regardless of the test duration
When gas bubbles appear after immersion in water
When it has been checked with a fixed electronic detector

271

Medium

Which legal act currently sets out the obligation to check stationary refrigeration equipment containing F-gases for leaks, and how often this must be done?


Implementing Regulation (EU) 2024/2215
Regulation (EU) 2024/573
Regulation (EU) No 517/2014
Commission Regulation (EC) No 1516/2007

272

Difficult

Which parts of a refrigeration system should be given particular attention during a leak check?


Only condenser connections, because the refrigerant is liquid there
Joints, valves incl. stems, seals, parts subject to vibration, connections to safety devices
Compressor and receiver connections, because the pressure is highest there
Only compressor connections, because they are the only parts subject to vibration

273

Easy

What is the superheat of refrigerant vapour?


The amount of heat required to evaporate a liquid
The difference between the condensing temperature and the ambient temperature
The difference between the saturation temperature and the actual liquid temperature in the liquid line
The difference between the actual vapour temperature and the saturation temperature corresponding to its pressure (expressed in K)

274

Difficult

Leak checks can be carried out using various methods. Which pair is correct?


Physical and chemical methods
Methods with and without quality control of supplies
Direct and indirect methods
Material quality control methods and electronic methods

275

Difficult

To whom can leak checks of stationary refrigeration equipment containing F-gases be entrusted?


An employee appointed by the owner of the installation
A person who has carried out such checks before
A natural person holding a certificate covering leak checks (A1, A2 within its charge limit, or E)
Any leak-testing specialist

276

Difficult

What conditions must be met to use UV dye for leak checking?


Manufacturer approval of the method and a certificate covering breaking into the circuit
A UDT authorisation for pressure testing is required
It is sufficient that introducing dye into the circuit is technically feasible
It is sufficient to have a UV lamp, dye and safety goggles

277

Difficult

Which leak-checking methods are considered direct methods?


Pressure-change measurement and immersion in water
Vacuum test and foam solution
Nitrogen with tracer gas and pressure measurement
1. gas detection devices (portable or fixed leak detection system), 2. UV detection fluid or dye, 3. bubble/foam solutions

278

Difficult

What do indirect leak-checking methods involve?


Leak detection with an electronic detector
Ultrasonic measurement
A visual and manual check and analysis of parameters: pressure, temperature, compressor current, liquid levels and recharge volume
Leak detection with UV dye

279

Medium

How should the pressure be increased during a pressure tightness test?


As quickly as possible
In one step, by fully opening the nitrogen cylinder valve
Gradually, in stages, checking for leaks at each level until the test pressure is reached
In any way

280

Medium

What electronic equipment should be used for leak checking?


Only detectors with an infrared sensor
Only devices with an 'ion pump' sensor
Only hot-cathode devices
Detectors suited to the refrigerant in the system, with appropriate sensitivity, checked periodically

281

Medium

What documentation should be checked before starting a leak check?


The operator's fixed-asset inventory ledger
Only the installation invoice and the first start-up report
The equipment records – especially recurring problems and previous leaks
Attendance sheets of the plant-room staff for the year

282

Medium

What information must be recorded in the leak check report?


Only the number of leaks found and the date of the check
Date, number and location of leaks, how they were repaired, technician details and signature
The date, a general note about the leak and the operator's signature
The method used, the time spent on site and the cost of repair

283

Medium

What pressure should be used for the pressure tightness test?


A pressure not exceeding the maximum allowable pressure of the system (PS)
Always 10–12 bar
Any pressure, at the technician's discretion
Always 2–3 bar

284

Medium

What is the temperature glide of a refrigerant?


The temperature rise of the vapour in the compressor
A property of single-component refrigerants, for which one saturation temperature corresponds to a given pressure
In zeotropic mixtures, the difference between the temperatures at the start and end of a phase change (boiling or condensation) at constant pressure
The temperature drop of the refrigerant across the expansion valve

285

Difficult

What does a vacuum (decay) test involve?


The pump is restarted every time the system pressure rises
After isolating the pump, you check whether the system pressure rises
With the pump running, you watch the vacuum gauge reading
The pump runs continuously to hold the required vacuum for the test

286

Difficult

How often should leak tests be carried out on equipment containing 1.5 kg of R404A refrigerant (5.9 tonnes of CO₂ equivalent)?


Once every six months.
Only when servicing the unit.
At least once every 12 months.
On initial commissioning.

287

Difficult

How often should leak tests be carried out on equipment containing 7 kg of R404A refrigerant (27.45 tonnes of CO₂ equivalent)?


Once every six months.
On initial commissioning.
Only when servicing the unit.
At least once every 12 months.

288

Medium

In which equipment is a leakage detection system required?


Equipment with ≥ 500 t CO₂ eq of Annex I F-gases (or ≥ 100 kg of Annex II Section 1 gases)
Equipment with 5 t CO₂ eq or more of F-gases, regardless of equipment type
Equipment with 30 kg or more of F-gases, regardless of their GWP
Equipment with 50 t CO₂ eq or more of F-gases, regardless of equipment type

289

Difficult

Under Regulation (EU) 2024/573, a leakage detection system is mandatory when:


the charge is 100 kg or more of ozone-depleting substances
the F-gas charge of the refrigeration equipment is 500 t CO₂ eq or more
the equipment contains a flammable refrigerant in any quantity
the equipment operates in an enclosed space

290

Difficult

Which leak-checking method may NOT be used by a holder of a Category E certificate?


Checking with a foaming solution
Visual inspection
Leak checking with a fluorescent dye introduced into the circuit
Measurement with a handheld electronic detector

291

Medium

What should you check before using a portable electronic leak detector?


That it has an infrared sensor, as only this type is permitted
That it suits the refrigerant and has been checked as the manufacturer requires
That it has been zeroed close to the suspected leak point
That it holds a valid UDT inspection certificate

292

Medium

Which certificate types (A1, A2, B, C, D, E) authorise leak checks of equipment containing F-gases?


All except D
Only E
A1, A2 and E
Only A1 and A2

293

Difficult

Within what timeframe must a leak test be carried out on a stationary refrigeration system after a leak has been repaired, in accordance with EU Regulation 2024/573 on F-gases?


At the next periodic inspection.
Immediately after the repair.
At any time.
Between 24 hours and 1 month after the repair.

294

Difficult

How often must refrigeration equipment containing ≥500 t CO₂ eq of F-gases be checked if (contrary to Article 6) no leakage detection system is installed?


Every 3 months
Every 12 months
Every month
Every 6 months

295

Medium

Why is it advisable to subcool the liquid refrigerant?


To ensure that liquid free of vapour bubbles enters the expansion valve
To allow a smaller expansion valve to be used
To lower the evaporating temperature in the evaporator
To allow a condenser with a smaller heat-exchange surface to be used

296

Medium

What must be done after repairing a leak in the refrigeration unit of a refrigerated trailer?


Visually inspect only the bolted and brazed joints near the repair
Update the equipment records and carry out a leak check (it may be done directly after repair)
Issue the invoice and leave the leak check to the next periodic service
Charge an alternative refrigerant, start up and measure the parameters

297

Medium

Recovery of fluorinated greenhouse gases means:


The final decommissioning and withdrawal from service or use of a product or piece of equipment containing fluorinated greenhouse gases.
The collection and storage of fluorinated greenhouse gases from containers, products and equipment during maintenance or servicing or prior to their disposal.
The reuse of fluorinated greenhouse gases following a basic purification process.
The reprocessing of fluorinated greenhouse gases to achieve their specified standard properties.

298

Medium

Who is authorised to recover refrigerant from stationary refrigeration equipment containing F-gases?


The administrator of the operator's account in the register
The operator
The owner of the installation
A natural person holding a certificate of the relevant type (A1; A2. or D within their charge limit)

299

Medium

How must recovered refrigerants be stored?


In a labelled recovery cylinder with a dual valve and a valid inspection
In any used refrigerant cylinder, provided it is leak-tight
In any pressure vessel that has some form of approval
In a disposable (non-refillable) cylinder that held the same refrigerant

300

Medium

When should the recovery of fluorinated greenhouse gases be carried out:


Before the final disposal of equipment and, where applicable, during its servicing and maintenance.
Always during servicing and maintenance of equipment.
Before each leak test of the equipment.
Only prior to the final disposal of equipment.

301

Medium

What should be done if recovered refrigerant is contaminated (e.g. with acid, air or moisture)?


Hand it over to a specialised, authorised company for reclamation or destruction
Pass it through a particle filter and reuse it
Add a special contaminant neutraliser
Clean the mixture yourself using a filter-drier

302

Medium

What should be done if different refrigerants have been mixed in a storage cylinder?


Pass it through a filter-drier and reuse it
Separate the mixture into its components yourself
Hand the mixture over to an authorised company – as a rule for destruction
Add a special refrigerant to the mixture

303

Medium

How does push-pull refrigerant recovery work?


Nitrogen is injected into the system, pushing the refrigerant into the atmosphere
Refrigerant is drawn alternately from the suction and discharge sides of the compressor
The recovery unit draws vapour from the recovery cylinder and pushes it into the system; the pressure difference forces liquid refrigerant out of the system into the cylinder
The recovery unit draws vapour from the system and condenses it in the cylinder

304

Medium

What are the options for managing waste refrigerant?


Disposal, storage
Recovery, disposal
Reclamation, recovery
Recycling, reclamation, destruction

305

Medium

Which management option restores recovered refrigerant to a quality equivalent to virgin product, so that it can be used by any undertaking?


Storage
Destruction
Recycling
Reclamation

306

Medium

The lower the evaporating temperature, …


…the greater the density of the suction vapour and the lower the refrigerant mass flow rate
…the lower the density of the suction vapour and the lower the refrigerant mass flow rate
…the greater the density of the suction vapour and the greater the refrigerant mass flow rate
…the lower the density of the suction vapour and the greater the cooling capacity of the compressor

307

Medium

How must transportable pressure vessels (e.g. refrigerant cylinders) be marked?


Only with weight and capacity marks
With the manufacturer's logo and date of manufacture
Among other things: the number of the design and testing standard, marks of the approving country and the inspection body, the date of the initial inspection, and the manufacturer's and operational marks
The marking is optional

308

Medium

The recovery of refrigerants does not require the use of:


A refrigerant recovery station.
Hoses with shut-off valves.
An electronic leak detector.
Scales with a measurement range suitable for the size of the cylinder being filled.

309

Medium

What functions does the compressor perform in a refrigeration system?


The compressor creates a vacuum on the suction side of the system
The compressor compresses ambient air and increases the pressure of the refrigerant.
The compressor condenses the refrigerant.
The compressor draws in refrigerant vapour from the evaporator, compresses it, and then forces it into the condenser, raising the pressure to the required condensing pressure.

310

Easy

What is the compression ratio of a compressor?


The ratio of suction pressure to discharge pressure (po/pc)
The ratio of absolute discharge pressure to absolute suction pressure (pc/po)
The amount of refrigerant compressed per cycle relative to heat capacity
The ratio of discharge pressure to the effective capacity of the compressor (p/Vk)

311

Medium

What is compressor flooding (liquid slugging)?


Flooding of the compressor by rainwater
Liquid refrigerant or oil entering the compression chamber
Excess oil in the condenser
A large amount of liquid refrigerant in a flooded evaporator, which is a normal operating condition

312

Medium

Within what range is the compressor motor speed typically controlled using a frequency inverter?


By a maximum of 10%
From approximately 10% to 90% of nominal capacity
Approximately 30 to 75 Hz, corresponding to about 60–150% of nominal capacity (depending on the compressor manufacturer)
Speed control does not change the cooling capacity

313

Easy

What is the theoretical displacement (swept volume flow) of a compressor?


A value expressed by the coefficient of performance (COP)
The volume of vapour drawn in per unit of time, determined by the compressor's geometry and speed (stated by the manufacturer, e.g. in m³/h)
The volume of a single cylinder in cm³
The volume of refrigerant flowing in one piston cycle under actual operating conditions

314

Medium

Why is it essential to observe the correct phase sequence for scroll compressors and screw compressors?


Because this type of compressor has difficulty starting up if the phase sequence is changed.
Because the motor speed would decrease, and consequently the compressor’s capacity.
Because changing the phase sequence would reverse the direction of rotation of the compressor rotors, which could result in damage to the compressors.
Because these types of compressors are sensitive to voltage drops.

315

Medium

What compression ratio should each stage of a two-stage vapour-compression system have (rule of thumb)?


Less than approximately 8
Greater than 10
Equal to 1
Greater than 18

316

Medium

Why is a shaft seal necessary in open-type compressors?


To prevent air from entering and refrigerant from leaking out of the compressor
Only to prevent oil leakage
To protect the crankshaft bearing
To ensure the bearing remains lubricated

317

Medium

How can you check whether the liquid refrigerant is sufficiently subcooled?


Check whether the whole evaporator surface is covered with an even layer of frost
Check by touch whether the condenser outlet is noticeably colder than ambient
Check whether the liquid distributor upstream of the evaporator feels warm
Compare the liquid-line temperature with the saturation temperature at the measured condensing pressure

318

Medium

Why is the compressor crankcase heated?


To increase dissolution of refrigerant in the oil and improve its viscosity
To dehydrate the oil
To limit refrigerant migration into, and dissolution in, the oil during standstill
To keep the lubricating oil liquid

319

Easy

What is the clearance (dead) volume of a reciprocating compressor?


The volume between the valve plate and the piston at bottom dead centre
The volume between the valve plate and the piston crown at top dead centre
The space between the underside of the piston and the crankcase cover
The space between the side of the piston and the cylinder

320

Medium

What are compressor packs (racks)?


Several air-cooled condensers
Sets of compressors connected in any configuration
Several compressors connected in parallel on a common frame with common suction and discharge headers
Units with two-stage compressors

321

Medium

What is the main advantage of multi-compressor packs?


No need for compressor controls and safety devices
Low purchase cost and easy installation without special controls
Stepwise capacity matching to demand, plus redundancy
A smaller refrigerant charge than a single-compressor system

322

Medium

What is meant by the operating envelope (application range) of a compressor?


A range determined only by the evaporating temperature
The capacity, refrigerant type and dimensions of the compressor
A range determined by the evaporating temperature at a given ambient temperature
The permissible range of evaporating and condensing temperatures (to, tk), or the corresponding pressures, within which the compressor may operate

323

Medium

What are the basic functions of oil in a compressor?


Increasing the cooling capacity of the refrigerant
Sealing leaks that develop in the installation
Lubricating bearings and sliding surfaces, removing heat, and sealing clearances (e.g. between piston and cylinder, or rotors)
Absorbing moisture from the refrigerant

324

Medium

What are the most effective ways of controlling compressor cooling capacity?


Partially covering the evaporator
Changing the displacement: varying the rotational speed or unloading cylinders
Pressure control valves
An expansion valve

325

Medium

What does hot-gas bypass capacity control involve?


High-pressure liquid is injected into the suction to increase capacity
Bypass is not used for capacity control
The compressor speed is varied
Part of the hot discharge gas is passed through a bypass valve to the suction side (or evaporator inlet), reducing the effective capacity

326

Medium

What is the fundamental difference between hermetic and semi-hermetic compressors?


Semi-hermetic compressors run more quietly as a complete unit
The semi-hermetic casing is bolted (can be opened); the hermetic one is welded
The semi-hermetic compressor has no motor inside the casing
Both can be dismantled; they differ only in cooling capacity

327

Medium

How does a scroll compressor work?


A scroll compressor is also known as a turbo compressor.
It is a type of piston-type device.
It uses two screws to compress the refrigerant.
It is a positive-displacement compressor in which compression results from the interaction of a fixed and an orbiting scroll.

328

Medium

What physical process takes place in the evaporator?


The refrigerant is subcooled as a liquid
The secondary fluid (glycol, water) evaporates while the refrigerant condenses
The liquid refrigerant evaporates, absorbing heat, and the vapour is slightly superheated at the outlet
The refrigerant condenses

329

Medium

What is the purpose of compressor capacity control?


To increase the condensing pressure
To match capacity to the condensing temperature
To match the cooling capacity to the current demand
To ensure compressor lubrication

330

Medium

Why is inverter speed control advantageous for refrigeration compressors?


Reducing the speed improves oil return to the compressor
It enables continuous, smooth control of cooling capacity
It increases compressor capacity above nominal at any frequency
It can be used with any compressor to ensure lubrication

331

Medium

Does the suction gas temperature affect the cooling capacity of the compressor?


Yes, but only in reciprocating compressors, not scroll
Yes, but only if the suction gas is deeply cooled
Yes – higher temperature lowers vapour density, mass flow and capacity
No – capacity depends only on the compressor displacement

332

Medium

In the case of compressor units fitted with an oil level control system, is it necessary to install the compressors at the same height?


Only screw compressors.
No.
Only scroll compressors.
Yes.

333

Medium

What functions does a compressor powered by the vehicle’s engine perform in a transport refrigeration system?


This compressor condenses the refrigerant whilst the vehicle is in motion.
This compressor creates a vacuum on the suction side of the system whilst the vehicle’s engine is switched off.
The compressor compresses ambient air and increases the pressure of the refrigerant.
This compressor draws in refrigerant vapour from the evaporator, compresses it and then forces it into the condenser whilst the vehicle’s engine is running.

334

Medium

Which media most commonly absorb heat from the refrigerant in the condenser?


Only a water–glycol mixture
Air or water
Ammonia
Air and CO₂

335

Medium

What is the function of the condenser in refrigeration systems?


Releasing only the heat from the compressor into the surroundings
Releasing to the environment the heat absorbed in the evaporator and the heat added during compression
Absorption of heat rejected in the regenerative heat exchanger
Releasing only the heat absorbed in the evaporator into the surroundings

336

Medium

If the refrigerant temperature on the high-pressure side is above its critical temperature, condensation…


…always occurs regardless of temperature
…does not depend on temperature
…occurs provided a special condenser is used
…does not occur

337

Medium

How is liquid subcooling usually achieved in a refrigeration system?


In the final section of the condenser (or in an additional subcooler)
By dissolving the refrigerant in oil
With an additional heat exchanger using liquid nitrogen
With hot high-pressure vapour

338

Medium

What is the purpose of condenser fan speed control?


Only to protect against exceeding the maximum condensing pressure
To keep the condensing pressure at the correct level
To reduce energy efficiency
To disperse refrigerant in the event of a leak

339

Medium

Which international agreement introduced the global phase-down of HFC production and consumption?


The Paris Agreement
The Kyoto Protocol
The Kigali Amendment to the Montreal Protocol
The Vienna Convention for the Protection of the Ozone Layer

340

Medium

Which international treaty governs the phase-out of ozone-depleting substances (CFCs, HCFCs)?


The UN Framework Convention on Climate Change (UNFCCC)
The Montreal Protocol
The Stockholm Convention
The Paris Agreement

341

Difficult

What is the basis of the GWP values in Regulation (EU) 2024/573?


AR4 for all substances
Each Member State sets its own GWP values
AR6 for all substances
For HFCs (Annex I) – mainly the IPCC Fourth Assessment Report (AR4); for HFOs and non-fluorinated substances (Annexes II and VI) – the Sixth Assessment Report (AR6)

342

Difficult

An air conditioner (not hermetically sealed) contains 2.5 kg of R410A (GWP 2088). How often must it be checked for leaks?


At least every 12 months (5.22 t CO₂ eq)
Every 3 months
Every 6 months
No checks required (below 3 kg)

343

Difficult

When is labelled hermetically sealed equipment containing HFCs (Annex I) exempt from leak checks?


Always, regardless of charge
When it contains less than 5 t CO₂ eq
Never – hermetically sealed equipment is always checked
When it contains less than 10 t CO₂ eq, and in residential buildings also when it contains less than 3 kg of F-gases

344

Difficult

Is a chiller containing 50 kg of R1234ze(E) subject to leak checks under Regulation (EU) 2024/573?


Yes – at least every 6 months (every 12 months with a leakage detection system)
Yes – every 12 months, because its GWP is low
No – HFOs are not subject to leak checks
No – the threshold is 5 t CO₂ eq and 50 kg of R1234ze is below 1 t CO₂ eq

345

Difficult

In 2026, may an existing refrigeration installation using R404A (GWP 3922) be topped up with virgin refrigerant?


Yes – the ban applies only to equipment ≥40 t CO₂ eq
Yes, if the equipment has a leakage detection system
No – only reclaimed or recycled R404A is allowed (until 1 January 2030)
Yes – bans apply only to new equipment

346

Difficult

After 1 January 2026, may an R410A (GWP 2088) air conditioner be serviced using virgin R410A?


Yes – the servicing ban for air conditioners and heat pumps covers F-gases with GWP ≥ 2500
Only with reclaimed refrigerant
No – the ban covers all HFCs
No – the ban covers all refrigerants with GWP ≥ 750

347

Medium

Can HFC refrigerant recovered during a repair be put straight back into the same equipment without any cleaning (filtering/drying)?


Yes, always
Yes, if the operator agrees
No – recovered F-gas may be used for filling only after it has been recycled or reclaimed
Yes, if less than 24 hours have passed

348

Medium

Who may purchase HFCs for servicing refrigeration equipment?


Any business
Any adult
Only the equipment operator
Only a person holding the relevant certificate or an undertaking employing such persons

349

Medium

Under what condition may non-hermetically sealed split air conditioning charged with F-gas be sold to an end user?


Only if the unit contains less than 3 kg of refrigerant
When evidence is provided that installation will be carried out by a certified undertaking
When the user signs a statement that they will install it themselves
Unconditionally

350

Medium

By when must the holder of an F-gas certificate issued under Regulation (EU) No 517/2014 first complete refresher training or an evaluation process?


By 12 March 2029 (and then at least every 7 years)
Never – the certificate is valid indefinitely
By 12 March 2025
By 31 December 2030

351

Medium

What must the holder of a Category I certificate (Regulation 2015/2067) do to continue using it?


Apply for an extension without training
Update their knowledge and skills to the level of Certificate A1 (Annex I to Regulation 2024/2215)
Nothing – Category I automatically becomes A1
Update their knowledge to the level of Certificate E

352

Medium

What does Certificate C under Implementing Regulation (EU) 2024/2215 authorise?


Leak checks without breaking into the circuit
Recovery of F-gases from equipment <3 kg
All activities in Article 2(1) in relation to ammonia (NH₃)
All activities in relation to CO₂

353

Medium

May a person enrolled in a certification training course carry out certified activities?


Yes – independently, for 6 months
Yes – with no time limit, if employed by a certified company
No, never
Yes – under the supervision of a certified person, for no more than 24 months in total

354

Medium

How long must the operator keep the records of equipment subject to leak checks, if they are not kept in a national database?


At least 1 year
Until the equipment is decommissioned
At least 2 years
At least 5 years

355

Difficult

Since 1 January 2025, may a new single-split air conditioner containing 1.5 kg of R410A be placed on the market?


Yes, if the unit is hermetically sealed
Yes – the ban applies from 2029
No – single splits <3 kg with F-gases of GWP ≥ 750 are banned
Yes – the ban applies only to units >12 kW

356

Difficult

From when is it prohibited to place on the market split air-to-air systems up to 12 kW containing F-gases with GWP ≥150 (unless required for safety)?


From 1 January 2029
From 1 January 2027
From 1 January 2035
From 1 January 2025

357

Difficult

Which persistent atmospheric degradation product of R1234yf is classed as a PFAS?


Carbon dioxide
Carbonic acid
Ozone
Trifluoroacetic acid (TFA)

358

Medium

What distinguishes class 2L refrigerants from class 2?


No lower flammability limit
A maximum burning velocity of no more than 10 cm/s
Heat of combustion above 19 MJ/kg
Higher toxicity

359

Medium

What is the lower flammability limit (LFL) of propane R290?


Approx. 0.38 kg/m³
Approx. 0.038 kg/m³ (approx. 2.1% by volume)
Approx. 1.8 kg/m³
Approx. 0.307 kg/m³

360

Difficult

What is the maximum R290 charge per circuit of a commercial refrigerating appliance (e.g. a cabinet) according to EN IEC 60335-2-89:2022?


13 × LFL ≈ 494 g
1.5 kg
150 g
1.2 kg

361

Difficult

Calculate the maximum R32 charge (LFL = 0.307 kg/m³) for a wall-mounted air conditioner (h₀ = 1.8 m) in a 20 m² room using m_max = 2.5 × LFL^1.25 × h₀ × A^0.5.


approx. 1.5 kg
approx. 4.6 kg
approx. 0.46 kg
approx. 13.8 kg

362

Medium

Equipment marked 'Ex II 3G' may be used in zone:


0
1
20 (dusts)
2 (explosive gas atmosphere unlikely and short-lived)

363

Medium

How is explosion hazard zone 2 defined?


An area where flammable refrigerants are never used
An explosive atmosphere is not likely in normal operation and, if it occurs, persists only for a short period
An explosive atmosphere is present continuously or for long periods
An explosive atmosphere is likely to occur in normal operation

364

Medium

Under which UN number is propane (R290) carried under ADR?


UN 1005
UN 3337
UN 3252
UN 1978

365

Difficult

What is the maximum quantity of R290 (class 2, group F) that may be carried per transport unit under the ADR 1.1.3.6 exemption?


20 kg
1000 kg
Unlimited
333 kg

366

Medium

At what concentration should a portable flammable gas detector used for R290 work raise an alarm at the latest?


At 100% of LFL
No higher than 25% of LFL
At 150% of LFL
At 5% propane by volume

367

Medium

How should a recovery cylinder be prepared before filling it with a hydrocarbon refrigerant?


No preparation is needed
Evacuate it (no air) and label it for the specific flammable refrigerant
Partly fill it with nitrogen to 5 bar
Purge it with compressed air

368

Medium

What is the correct approach in a risk analysis before work on an HC system?


Having a fire extinguisher is sufficient
First select PPE, then possibly remove ignition sources
The risk analysis is done after the work is finished
First eliminate hazard sources (e.g. ignition sources); where this is not possible, identify them and apply mitigating measures (ventilation, detection, PPE)

369

Difficult

What is the charge limit m₃ = 130 m³ × LFL for R290 (LFL = 0.038 kg/m³) according to IEC 60335-2-40?


approx. 0.99 kg
approx. 4.94 kg
approx. 0.15 kg
approx. 13 kg

370

Medium

Which property of ammonia helps people detect a leak early?


It is denser than air
It is yellow in air
A very low odour threshold (a few ppm)
It is odourless

371

Medium

What hazard does a large CO₂ leak in an enclosed room pose to people?


CO₂ is completely safe
Explosion of the mixture with air
Accumulation near the floor and asphyxiating/toxic effects at high concentrations
Formation of hydrogen fluoride

372

Difficult

Why does the efficiency of transcritical CO₂ systems fall in warm climates, and how is this mitigated?


Efficiency does not depend on climate
At high ambient temperatures the system operates transcritically with large throttling losses – parallel compression and ejectors are used, among others
Gas cooler pressure drops – extra charge is added
CO₂ freezes in the gas cooler – heaters are used

373

Medium

What is floating head pressure and what does it achieve?


It means switching condenser fans off periodically
It increases subcooling by flooding the condenser
It lets the condensing pressure fall with ambient temperature, reducing compressor work and raising COP (requires an expansion valve that works at a small pressure difference)
It keeps a constant high condensing pressure all year

374

Medium

How do SEER/SCOP differ from EER/COP?


SEER/SCOP apply only to natural-refrigerant equipment
There is no difference – they are synonyms
SEER/SCOP are seasonal indicators accounting for part load and climate (EN 14825); EER/COP refer to a single operating point (EN 14511)
EER/COP are always higher than SEER/SCOP

375

Medium

Which design approach can significantly reduce the F-gas charge of a large refrigeration installation?


Omitting pipe insulation
An indirect (secondary-coolant) system or a cascade with a natural refrigerant in the low stage, plus heat exchangers with small internal volume
Adding a second liquid receiver
Larger liquid-line diameters

376

Medium

Why must the charge of small, critically charged R290 systems be weighed to within a few grams during service?


Because R290 is more expensive than HFCs
Because scales are not needed – charging is done by sight glass
Because extra R290 improves efficiency
Small charge deviations significantly change superheat/subcooling and efficiency, and overcharge increases the risk in a leak

377

Medium

Which information must be entered in the equipment records after a leak check?


The date and result of the check and the identity of the undertaking and person who performed it (with certificate number)
Only the equipment's energy consumption
Only the date of the check
Only the operator's signature

378

Medium

What must be done when an indirect method (e.g. parameter analysis) indicates a possible leak?


Record it and check at the next periodic inspection
Carry out a direct-method examination to locate the leak
Nothing – indirect methods are sufficient
Top up the refrigerant and end the check