1

Stredne ťažká

Why is ammonia (R717) classed as a toxic refrigerant?


Because it is heavier than air and displaces oxygen
Because it is colourless and odourless and therefore hard to detect
Because it does not react with water, making neutralisation difficult
It severely irritates the respiratory tract, eyes and skin, and is poisonous when inhaled at higher concentrations

2

Ťažká

What is the main difference between a dry-expansion and a flooded evaporator?


In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)
A dry-expansion evaporator is filled with liquid, a flooded one with vapour
A dry-expansion evaporator always has a lower pressure than a flooded one
A dry-expansion evaporator needs no expansion valve, a flooded one does

3

Ťažká

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Below atmospheric (approx. 0.7 bar abs at −40 °C)
Positive pressure of 5–10 bar
Positive pressure of 10–20 bar
Atmospheric pressure, approx. 1 bar abs

4

Ľahká

What is the basic requirement when charging a system with R717 (NH₃)?


Charging can be carried out without personal protective equipment
Charging should take place in a well-ventilated area using appropriate personal protective equipment
NH₃ can be charged together with air
Charging must only take place at temperatures below 0°C

5

Ťažká

How is oil managed in R717 systems?


Oil requires no monitoring
Oil has no effect on system operation
Oil can be mixed with any refrigerant
Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer

6

Ľahká

What is the correct procedure for recovering R717 from a system?


The refrigerant can be drained into the sewer system
The gas can be released into the atmosphere
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
Recovery is not required

7

Ľahká

How should R717 (NH₃) be stored?


Near heat sources
In unmarked plastic containers
In any open containers
In sealed, labelled containers, in a cool and well-ventilated place

8

Ťažká

What should be done with contaminated R717?


Purify it or send it for disposal in accordance with regulations
Release it into the atmosphere
Continue to use it without restriction
Dilute it with water and reuse it

9

Ľahká

What is the main hazard associated with an R717 leak during maintenance work?


Increased cooling efficiency
Toxic to humans and may cause chemical burns
No risk whatsoever
Damage to electrical equipment only

10

Ťažká

What should be done if an NH₃ leak is detected?


Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)
Carry on working wearing a dust mask
Carry on working with the room door open
Increase the pressure in the system

11

Ťažká

What role do scrubbers play in NH₃ systems?


They are used to measure temperature
Neutralise ammonia through absorption in a liquid (e.g. water)
They increase the pressure in the system
They store the refrigerant

12

Ťažká

How should the system be prepared before filling with R717?


Check for leaks, remove air and moisture, and create a vacuum
The pressure must be increased above the standard level
There is no need to check it
Simply start it up

13

Ťažká

What are the transport requirements for R717?


It can be carried without labelling
Transport is not regulated
It can be carried in open containers
It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)

14

Ľahká

What personal protective equipment is required when working with NH₃?


No requirements
Workwear only
Only a safety helmet
Safety goggles, gloves and respiratory protective equipment

15

Ťažká

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)
An oil return line cannot be used in R717 systems because the oil is too hot
R717 does not mix with the oil; the oil collects on the high-pressure side above the R717
R717 mixes very well with the oil, which easily returns to the compressor

16

Ťažká

Which refrigerant can be detected with phenolphthalein paper?


R717
R744
R1270
R1234ze(E)

17

Ťažká

Which system may require manual oil recovery?


Supercritical ‘booster’ system using R744
An R717 system
Secondary system using R744
R744 cascade system

18

Ťažká

Which refrigerant is lighter than air?


R717
R1270
R1234ze(E)
R744

19

Ťažká

R717 is highly corrosive to:


stainless steel
aluminium
titanium
copper (and its alloys)

20

Ťažká

What is the recommended pre-alarm level for fixed leak detection systems for R717?


5,000 ppm
500 ppm
500,000 ppm
50,000 ppm

21

Ťažká

Why are compressors with a separate motor (open type) mostly used in R717 systems?


To increase the refrigerant charge
Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used
To lower the condensing pressure
Because they are cheaper

22

Ťažká

Which type of compressor is most commonly used in large ammonia systems?


A reciprocating or screw compressor
Diaphragm compressor
Hermetic scroll
Rotary vane compressor

23

Ťažká

How is the capacity of a piston compressor regulated in NH₃ systems?


By increasing the condensing pressure
By reducing the refrigerant charge
By unloading the cylinders or changing the rotational speed
Solely by adjusting the oil volume

24

Ťažká

How is the capacity of a screw compressor most commonly controlled?


By using a slide valve
By changing the type of oil
By adjusting the oil level
By closing the suction valve

25

Ťažká

When is two-stage compression used in NH₃ systems?


Only with water-cooled condensers
At low evaporating temperatures (pressures) and high pressure ratios
Only in small systems
At small temperature differences

26

Ťažká

What is the advantage of two-stage compression over single-stage compression?


Lower efficiency
No need for a separator
Higher energy consumption
Higher efficiency and lower discharge temperature

27

Ťažká

How does an evaporative condenser used in NH₃ systems work?


It utilises the evaporation of water to increase cooling efficiency
Operates without a fan
It does not require a water supply
It transfers heat only to the air

28

Ťažká

What is the function of the liquid separator in an NH₃ system?


Increases the discharge temperature
It prevents liquid from entering the compressor
It separates oil from the refrigerant
Regulates the condensing pressure

29

Ťažká

What is the purpose of monitoring the liquid level in the separator?


To control the condenser fan
To reduce the condensing temperature
To increase the oil volume
To maintain the correct refrigerant level and prevent the compressor from flooding

30

Ťažká

What is the role of the float switch in NH₃ systems?


It is used to detect leaks
It regulates the condensation temperature
It monitors the liquid level in the tank or separator
It controls the fan’s operation

31

Ťažká

What is a thermosyphon in NH₃ systems?


A defrosting device
A type of safety valve
An oil circulation pump
A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling

32

Ťažká

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To increase the amount of refrigerant
Because the oil mixes only with water
To reduce the pressure
Because NH₃ does not mix with most compressor oils

33

Ťažká

What is the main function of an oil separator in NH₃ systems?


Removing moisture from the system
To lower the condensation temperature
To separate the oil from the refrigerant and return the oil to the compressor
To increase fan efficiency

34

Ťažká

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


A direct-expansion (DX) system
A pumped liquid-recirculation system
An indirect system
A glycol system

35

Ťažká

What is the characteristic feature of a flooded evaporator system?


The evaporator is filled exclusively with vapour
No level control is required
The evaporator contains a large amount of liquid, which improves heat transfer
No separator is used

36

Ťažká

What is the main difference between a direct and an indirect system?


In a direct system, there is no evaporator
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In an indirect system, NH₃ flows directly into the space being cooled
In an indirect system, no compressor is used

37

Stredne ťažká

Which property of ammonia helps people detect a leak early?


It is odourless
It is denser than air
It is yellow in air
A very low odour threshold (a few ppm)