F-Gas English Low GWP

Minden kérdés
HFC | Flammable | CO₂ | NH₃
Könnyű kérdések | Közepes nehézségű kérdések | Nehéz kérdések

1

Nehéz

Why do CO₂ refrigeration systems require special attention when separating liquid and oil?


CO₂ cannot be used in systems with sight glasses
CO₂ is flammable, so separators cannot be used
CO₂ does not require lubrication, so separators are unnecessary
CO₂ operates at high pressure, which increases the risk of compressor failure and leaks

2

Nehéz

What is the critical pressure of CO₂ (R744)?


Approximately 31 bar
Approximately 74 bar
Approximately 10 bar
Approximately 120 bar

3

Nehéz

What characterises the transcritical process in CO₂ systems?


It is irrelevant to the operation of the system
Conventional condensation occurs
The system operates above the critical point and the refrigerant does not condense in the conventional manner
It occurs only at low temperatures

4

Nehéz

What characterises the subcritical CO₂ process?


The absence of evaporation
Operation above the critical point
The conventional condensation process below the critical point
The absence of condensation

5

Nehéz

What is the log(p)-h diagram for CO₂ used for?


To detect leaks
For analysing thermodynamic processes in a refrigeration system
To measure temperature
To regulate pressure

6

Nehéz

What can be read from the log(p)-h graph?


Pressure, enthalpy, temperature and state of the refrigerant
Only the amount of refrigerant
Only the humidity
Only the temperature

7

Nehéz

What are CO₂ saturation tables used for?


To determine the relationship between temperature and pressure at saturation
To measure humidity
To determine the oil quantity
To regulate the compressor

8

Nehéz

What does the CO₂ saturation state mean?


A state of high pressure
Dry ice state
A state in which the refrigerant is only a gas
Equilibrium between the liquid and vapour phases

9

Nehéz

When can dry ice (solid CO₂) form?


In the event of a sudden drop in pressure and temperature below the triple point
At high temperature
At high pressure
During normal operation of the system

10

Nehéz

What risks are associated with the formation of dry ice in a CO₂ system?


Pressure reduction
Blocked pipes and system damage
Improved efficiency
No risk

11

Nehéz

How does the CO₂ pressure change as the temperature rises?


Rises sharply
It remains the same
It first decreases, then increases
It decreases

12

Nehéz

Why is understanding the log(p)-h graph particularly important for CO₂?


It only applies to NH₃
As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It doesn’t matter
It is only used for design purposes

13

Nehéz

What happens to CO₂ above the critical point?


It transitions to a supercritical state (no distinction between liquid and gas)
It turns into a solid
It ceases to conduct heat
It turns into a liquid

14

Nehéz

Why do CO₂ systems require precise pressure control?


Due to low pressures
They do not require control
Because there are no valves
Due to significant pressure changes with temperature fluctuations

15

Nehéz

What is the main characteristic of R744 (CO₂) refrigeration systems?


Low energy efficiency
Low operating pressures
Very high operating pressures
No need for regulation

16

Nehéz

What are the requirements for piping materials in CO₂ systems?


They may be made of any material
They must be made exclusively from plastics
They must be able to withstand high pressures (e.g. high-grade steel)
It does not matter

17

Nehéz

How does a booster system work in CO₂ installations?


It utilises two stages of compression (low and medium pressure) in a single system
It reduces the pressure in the evaporator
It is used to store the refrigerant
It reduces the amount of refrigerant

18

Nehéz

What is the function of high-pressure control valves in CO₂ systems?


They are used to store the refrigerant
They regulate oil flow
They control the pressure on the high-pressure side and optimise system operation
They lower the evaporator temperature

19

Nehéz

Why is pressure optimisation in CO₂ systems crucial?


It doesn’t matter
It enables the system to achieve maximum energy efficiency
It reduces the ambient temperature
It reduces the amount of refrigerant

20

Nehéz

What role do parallel-operating compressors play in CO₂ systems?


They lower the ambient temperature
They enable gas recovery from the medium-pressure stage and improve efficiency
They increase energy consumption
It does not matter

21

Nehéz

How does an ejector work in a CO₂ system?


It increases the amount of refrigerant
It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency
Stores the refrigerant
It lowers the evaporator temperature

22

Nehéz

What is the function of liquid ejectors in CO₂ systems?


They raise the refrigerant temperature
They reduce atmospheric pressure
They increase the amount of oil
They assist with liquid recovery and improve evaporator feed

23

Nehéz

What are the characteristics of partially flooded systems in CO₂ systems?


Low operating pressure
The presence of liquid in the evaporator, which improves heat transfer and efficiency
The absence of liquid in the evaporator
Lack of regulation

24

Nehéz

What is the main risk associated with static pressure in CO₂ systems?


Increased efficiency
A rise in pressure resulting from the refrigerant heating up whilst at rest
A drop in temperature
A decrease in refrigerant quantity

25

Nehéz

How can standstill pressure in CO₂ systems be reduced?


By using parallel compressors and external cooling systems
By increasing the refrigerant charge
By shutting down the system completely
By increasing the temperature

26

Nehéz

What does ‘stagnation’ of a refrigeration system mean in the context of CO₂?


A drop in temperature
Improved efficiency
Normal system operation
A lack of refrigerant flow, which can lead to increased pressure and safety risks

27

Nehéz

Why do CO₂ systems require more advanced automation than traditional systems?


They do not require automation
Due to low pressures
Because there are no valves
Due to the need for precise control of pressure and temperature

28

Nehéz

Which safety class applies to R744?


A3
B2L
A1
A2

29

Nehéz

In an R744 system operating in supercritical mode, the refrigerant entering the evaporator expansion valve is...


A supercritical fluid
Saturated vapour at intermediate pressure
A two-phase mixture at intermediate pressure
A subcooled liquid

30

Nehéz

In R744 supercritical systems, the gas cooler outlet valve controls:


The inlet temperature to the gas cooler
The gas cooler fans
The outlet temperature of the gas cooler
The pressure in the gas cooler

31

Nehéz

What is the main reason for using K65 copper tubing in some R744 systems?


They have good low-temperature performance
They bend easily
They can withstand higher pressures
They come in a wider range of diameters

32

Nehéz

Which of the following statements is correct regarding the installation of Schrader valves?


All Schrader valve cores are suitable for all refrigerants
Hydrocarbons leak through Schrader valves
Schrader valves must not be used in R744 systems
When brazing the valve body to the system, the core must be removed, then refitted and tightened to the correct torque

33

Nehéz

Which refrigerant can be detected using phenolphthalein paper?


R744
R1234ze
R717
R1270

34

Nehéz

How does a refrigerant shortage affect the high-pressure side of the system (without discharge pressure regulation)?


Discharge pressure will be lower, subcooling will be higher
The discharge pressure will be lower, and the subcooling will be lower
Discharge pressure will be higher, and the degree of subcooling will be higher
Discharge pressure will be higher, and the degree of subcooling will be lower

35

Nehéz

What is the benefit of using helium as a tracer gas in nitrogen during a pressure test?


It has a distinct odour
It has smaller molecules and diffuses more easily
It has a higher pressure than pure nitrogen
It is non-flammable

36

Nehéz

Why should an R744 system that has been drained be initially charged with the refrigerant in gaseous form?


To prevent the formation of dry ice
To ensure that R744 is charged slowly
To prevent damage to the compressor
To prevent the drain valve from opening

37

Nehéz

If an R744 system contains moisture because it has not been properly drained, what is the likely consequence?


The formation of carbonic acid, which will cause damage to the system
Reduced cooling capacity
The formation of hydrogen fluoride, which will decompose into hydrofluoric acid and damage the compressor
Excessively high discharge pressure

38

Nehéz

The pressure of R744 at a saturation temperature of 20 °C is approx.


14 bar g
25 bar g
56 bar g
90 bar g

39

Nehéz

At an ambient temperature of 25°C, the standby pressure in the low-pressure stage of an R744 cascade system will typically be…


Higher than the maximum permissible pressure in the low-pressure stage
The same as the pressure set on the relief valve
The same as the high-pressure setting on the pressure switch
27.5 bar g

40

Nehéz

What is the correct definition of critical temperature?


The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid
The temperature at which, for certain substances, electrical resistance is zero
The temperature above which there are no distinct liquid and gaseous phases
The temperature at which a substance changes from a gaseous to a solid state

41

Nehéz

In a supercritical system, under supercritical conditions, the working fluid in the gas cooler


loses heat at constant temperature and pressure
it loses heat as its temperature drops
it loses heat when its pressure drops
loses heat during a phase change